(T) Multi-Function Input Terminal Parameters
405
5
GROUP
T
Frequency setting voltage (current) bias/gain adjustment method
(a) Adjust any point with application of a voltage (current) between terminals 2 and 5 (4 and 5). (Frequency setting gain
adjustment example)
(b) Adjust any point without application of a voltage (current) between terminals 2 and 5 (4 and 5). (Frequency setting gain
adjustment example)
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Changing the operation mode
Select the PU operation mode.
3.
Selecting the parameter number
Read
Pr.903
for terminal 2.
Read
Pr.905
for terminal 4.
4.
Analog voltage (current) display
Press [A-SET]. The analog voltage (current) value (%) currently applied to the terminal 2 (4) is displayed.
Do not touch
until calibration is completed.
5.
Voltage (current) application
Apply a 5 V (20 mA) . (Turn the external potentiometer connected across terminals 2 and 5 (terminals 4 and 5) to a desired
position.)
6.
Setting completed
Press [SET] twice.
The analog voltage (current) value (%) adjustment is completed.
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Changing the operation mode
Select the PU operation mode.
3.
Selecting the parameter number
Read
Pr.903
for terminal 2.
Read
Pr.905
for terminal 4.
4.
Analog voltage (current) display
Press [A-SET]. The analog voltage (current) value (%) currently applied to the terminal 2 (4) is displayed.
5.
Analog voltage (current) adjustment
Press [SET]. Select the gain voltage (current) value (%) currently set in the parameter.
When
until the desired gain voltage (current) % is displayed.
6.
Setting completed
Press [SET].
The analog voltage (current) value (%) adjustment is completed.