707
Ready bit status selection (Pr.349, N240)
To select the error reset operation at inverter failure
• The status of Ready bit in communication data can be selected when a communication option (FR-A8ND, FR-A8NF, or FR-
A8NL) is installed.
• An error reset command from a communication option can be invalidated in the External operation mode or the PU
operation mode.
• The status of Ready bit is selectable.
The setting is available only when a communication option is installed.
Ready bit status selection (P.N240)
The status of Ready bit in communication data can be selected.
When either the external 24 V power supply or the control circuit power supply is ON.
• FR-A8ND
Class 0x29 Instance 1
• FR-A8NF
Inverter status monitor
Pr.
Name
Initial value
Setting range
Function
349
Communication reset
selection/Ready bit status
selection
0
0, 100
Error reset is enabled independently of
operation mode.
1, 101
Error reset is enabled in the Network operation
mode.
N010
Communication reset
selection
0
0
Enables the error reset function in any operation
mode.
1
Enables the error reset function only in the
Network operation mode.
N240
Ready bit status selection
0
0
The status of Ready bit in communication data
can be selected when a communication option
is installed.
1
Setting value
Description
Pr.349
N010
N240
Communication reset selection
Ready bit status selection
NET operation
mode
Other than NET
operation mode
Main circuit:
power-ON
Main circuit:
power-OFF
0
0
0
Reset enabled
Reset enabled
Ready bit: ON
Ready bit: ON
1
1
0
Reset enabled
Reset disabled
Ready bit: ON
Ready bit: ON
100
0
1
Reset enabled
Reset enabled
Ready bit: ON
Ready bit: OFF
101
1
1
Reset enabled
Reset disabled
Ready bit: ON
Ready bit: OFF
Attribute
ID
Access Name
Data
type
Number
of data
bytes
Initial
value
Range
Description
9
Get
Ready
BOOL
1
1
0
Other than the below
1
Pr.349
= "0, 1"
N240
= "0"
During stop / during acceleration /
during constant speed operation /
during deceleration / during reverse
rotation deceleration
Pr.349
= "100, 101"
N240
= "1"
During stop while the RY signal is ON /
during acceleration / during constant
speed operation / during deceleration /
during reverse rotation deceleration
Bit
Signal name
Description
14
READY signal
Reset cancel
Pr.349
= "0, 1"
N240
= "0"
0: During an inverter reset / during startup after power-ON.
1: During normal operation
Pr.349
= "100, 101"
N240
= "1"
0: RY signal is OFF
1: RY signal is ON