Appendix 1
For customers replacing the
conventional model with this
inverter
Appendix 1.1
Replacement of the FR-A700 series
Differences and compatibility with the FR-A700 series
Item
FR-A760
FR-A860
Control method
V/F control
Advanced magnetic flux vector control
Real sensorless vector control
Vector control (with plug-in option )
V/F control
Advanced magnetic flux vector control
Real sensorless vector control
Vector control (with plug-in option/control terminal
option)
PM sensorless vector control (IPM motor/SPM
motor)
Brake transistor
(brake resistor usable)
Built in for the FR-A760-00330 or lower
Built in for the FR-A860-01080 or lower
Maximum
o
u
tp
ut fr
eq
uen
cy
V/F control
400 Hz
590 Hz
Advanced
magnetic flux
vector control
120 Hz
400 Hz
Real sensorless
vector control
120 Hz
400 Hz
vector control
120 Hz
400 Hz
PM sensorless
vector control
―
400 Hz
PID control
Turn the X14 signal ON to enable PID control.
When the X14 signal is not assigned, just set a
value in
Pr.128
to enable PID control.
When the X14 signal is assigned, turn the X14
signal ON while
Pr.128
≠
"0" to enable PID control.
The PID pre-charge function and dancer control
are added.
Aut
o
matic restart after
ins
ta
n
tan
eous
pow
er
fa
ilu
re
Restart operation
Turn the CS signal ON to enable restart.
Restart is enabled by turning ON the CS signal, or
solely setting
Pr.57
if the CS signal is not assigned
to any input terminal.
Restart coasting
time
Time period from restoration of power until the
operation is restarted
Time period from occurrence of instantaneous
power failure until the operation is restarted
Number of motor poles
V/F control switching
The V/F switching signal (X18) is valid when
Pr.81
= "12 to 20 (2 to 10 poles)".
Pr.81
= "12 (12 poles)"
X18 is valid regardless of the Pr.81 setting. (The
Pr.81
settings "14 to 20" are not available.)
PTC thermistor input
Input from the terminal AU (The function of the
terminal AU is switched by a switch.)
Input from the terminal 2. (The function of the
terminal 2 is switched by the
Pr.561
setting.)
USB connector
B connector
Mini B connector
Control circuit terminal
block
Removable terminal block (screw type)
Removable terminal block (spring clamp type)
Terminal response level
The FR-A800's I/O terminals have better response level than the FR-A700's terminals. By setting
Pr.289
Inverter output terminal filter
and
Pr.699 Input terminal filter
, the terminal response level can be
compatible with that of FR-A700. Set to approximately 5 to 8 ms and adjust the setting according to the
system.
PU
Standard
FR-DU07 (4-digit LED)
None (FR-DU07 is not supported.)
Optional
FR-PU07
FR-LU08 (LCD)
FR-PU07 (Some functions, such as parameter
copy, are unavailable.)