Parameter List
Parameter list (by parameter number)
113
Pr.
List
5
─
792
F071
Deceleration time in low-speed
range
0 to 3600 s, 9999
0.1 s
9999
─
799
M520
Pulse increment setting for output
power
0.1, 1, 10, 100, 1000
kWh
0.1 kWh
1 kWh
─
800
G200
Control method selection
0 to 6, 9 to 14, 20,
100 to 106, 109 to 114
1
20
─
801
H704
Output limit level
0 to 400%, 9999
0.1%
9999
─
802
G102
Pre-excitation selection
0, 1
1
0
To
rq
u
e
comm
and
803
G210
Constant output range torque
characteristic selection
0, 1, 2, 10, 11
1
0
804
D400
Torque command source selection
0 to 6
1
0
805
D401
Torque command value (RAM)
600 to 1400%
1%
1000%
806
D402
Torque command value
(RAM,EEPROM)
600 to 1400%
1%
1000%
Sp
eed
l
imi
t
807
H410
Speed limit selection
0 to 2
1
0
808
H411
Forward rotation speed limit/speed
limit
0 to 400 Hz
0.01 Hz
60 Hz
809
H412
Reverse rotation speed limit/
reverse-side speed limit
0 to 400 Hz, 9999
0.01 Hz
9999
Torq
ue
lim
it
810
H700
Torque limit input method selection
0 to 2
1
0
811
D030
Set resolution switchover
0, 1, 10, 11
1
0
812
H701
Torque limit level (regeneration)
0 to 400%, 9999
0.1%
9999
813
H702
Torque limit level (3rd quadrant)
0 to 400%, 9999
0.1%
9999
814
H703
Torque limit level (4th quadrant)
0 to 400%, 9999
0.1%
9999
815
H710
Torque limit level 2
0 to 400%, 9999
0.1%
9999
816
H720
Torque limit level during
acceleration
0 to 400%, 9999
0.1%
9999
817
H721
Torque limit level during
deceleration
0 to 400%, 9999
0.1%
9999
Ea
sy gai
n
tu
ni
ng
818
C112
Easy gain tuning response level
setting
1 to 15
1
2
819
C113
Easy gain tuning selection
0 to 2
1
0
A
d
ju
stm
e
nt fu
nctio
n
820
G211
Speed control P gain 1
0 to 1000%
1%
60%
821
G212
Speed control integral time 1
0 to 20 s
0.001 s
0.333 s
822
T003
Speed setting filter 1
0 to 5 s, 9999
0.001 s
9999
823
G215
Speed detection filter 1
0 to 0.1 s
0.001 s
0.001 s
824
G213
Torque control P gain 1 (current
loop proportional gain)
0 to 500%
1%
100%
825
G214
Torque control integral time 1
(current loop integral time)
0 to 500 ms
0.1 ms
5 ms
826
T004
Torque setting filter 1
0 to 5 s, 9999
0.001 s
9999
827
G216
Torque detection filter 1
0 to 0.1 s
0.001 s
0 s
828
G224
Model speed control gain
0 to 1000%
1%
60%
829
A546
Number of machine end encoder
pulses
0 to 4096, 9999
1
9999
830
G311
Speed control P gain 2
0 to 1000%, 9999
1%
9999
831
G312
Speed control integral time 2
0 to 20 s, 9999
0.001 s
9999
832
T005
Speed setting filter 2
0 to 5 s, 9999
0.001 s
9999
833
G315
Speed detection filter 2
0 to 0.1 s, 9999
0.001 s
9999
834
G313
Torque control P gain 2
0 to 500%, 9999
1%
9999
835
G314
Torque control integral time 2
0 to 500 ms, 9999
0.1 ms
9999
836
T006
Torque setting filter 2
0 to 5 s, 9999
0.001 s
9999
837
G316
Torque detection filter 2
0 to 0.1 s, 9999
0.001 s
9999
Functio
n
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value
Refer
to
page
Customer
settin
g
Содержание 800 Series
Страница 11: ...MEMO 10 ...
Страница 17: ...MEMO 16 ...
Страница 95: ...MEMO 94 ...
Страница 671: ...MEMO 670 ...
Страница 681: ...MEMO 680 ...