(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
269
5
GROUP
F
5.8
(F) Setting of acceleration/deceleration
time and acceleration/deceleration pattern
5.8.1
Setting the acceleration and deceleration time
Purpose
Parameter to set
Refer
to page
To set the motor acceleration/
deceleration time
Acceleration/
deceleration time
P.F000 to P.F003,
P.F010, P.F011,
P.F020 to P.F022,
P.F030, P.F031,
P.F040, P.F070,
P.F071, P.G264
Pr.7, Pr.8, Pr.16,
Pr.20, Pr.21, Pr.44,
Pr.45, Pr.110, Pr.111,
Pr.147, Pr.611, Pr.791,
Pr.792, Pr.1103,
Pr.1349
To set the acceleration/
deceleration pattern suitable
for an application
Acceleration/
deceleration pattern and
backlash measures
P.F100,
P.F200 to P.F203,
P.F300 to P.F303,
P.F400 to P.F403
Pr.29,
Pr.140 to Pr.143,
Pr.380 to Pr.383,
Pr.516 to Pr.519
To command smooth speed
transition with terminals
Remote setting function P.F101
Pr.59
To set the starting frequency
Starting frequency and
start-time hold
P.F102, P.F103
Pr.13, Pr.571
,
To set optimum acceleration/
deceleration time automatically
Automatic acceleration/
deceleration
P.F500,
P.F510 to P.F513
Pr.61 to Pr.63, Pr.292
To set V/F pattern for lift
automatically
Lift operation
(Automatic acceleration/
deceleration)
P.F500, P.F510, P.F520 Pr.61, Pr.64, Pr.292
The following parameters are used to set motor acceleration/deceleration time.
Set a larger value for a slower acceleration/deceleration, and a smaller value for a faster acceleration/deceleration.
For the acceleration time at automatic restart after instantaneous power failure, refer to
Pr.611 Acceleration time at a
restart
Pr.
Name
Initial value
Setting range
Description
20
F000
Acceleration/deceleration
reference frequency
60 Hz
1 to 590 Hz
Set the frequency that will be the basis of
acceleration/deceleration time. As acceleration/
deceleration time, set the frequency change time from
a stop status to
Pr.20
.
21
F001
Acceleration/deceleration
time increments
0
0
Increment: 0.1 s
Select the increment for the
acceleration/deceleration time
setting.
1
Increment: 0.01 s
16
F002
Jog acceleration/
deceleration time
0.5 s
0 to 3600 s
Set the acceleration/deceleration time for JOG
operation (from stop status to
Pr.20
).
Refer to
611
F003
Acceleration time at a
restart
9999
0 to 3600 s, 9999
Set the acceleration time for restart (from stop status
to
Pr.20
).
When "9999" is set, standard acceleration time (like
Pr.7
) is applied as the acceleration time at restart.
Refer to
7
F010
Acceleration time
0 to 3600 s
Set the motor acceleration time (from stop status to
Pr.20
).
8
F011
Deceleration time
0 to 3600 s
Set the motor deceleration time (from
Pr.20
to stop
status).
44
F020
Second acceleration/
deceleration time
5 s
0 to 3600 s
Set the acceleration/deceleration time when the RT
signal is ON.
45
F021
Second deceleration time
9999
0 to 3600 s
Set the deceleration time when the RT signal is ON.
9999
Acceleration time = deceleration time
147
F022
Acceleration/deceleration
time switching frequency
9999
0 to 590 Hz
Set the frequency where the acceleration/deceleration
time switches to the time set in
Pr.44
and
Pr.45
.
9999
No function
110
F030
Third acceleration/
deceleration time
9999
0 to 3600 s
Set the acceleration/deceleration time when X9 signal
is ON.
9999
Third acceleration/deceleration is disabled.