Parameter List
Parameter list (by parameter number)
99
Pr.
List
5
Mot
o
r c
ons
ta
nt
s
80
C101
Motor capacity
0.4 to 55 kW, 9999
0.01 kW
9999
0 to 3600 kW, 9999
0.1 kW
81
C102
Number of motor poles
2, 4, 6, 8, 10, 12, 9999 1
9999
82
C125
Motor excitation current
0 to 500 A, 9999
0.01 A
9999
0 to 3600 A, 9999
0.1 A
83
C104
Rated motor voltage
0 to 1000 V
0.1 V
575 V
84
C105
Rated motor frequency
10 to 400 Hz, 9999
0.01 Hz
9999
85
G201
Excitation current refraction point
0 to 400 Hz, 9999
0.01 Hz
9999
86
G202
Excitation current low speed
multiplying factor
0 to 300%, 9999
0.1%
9999
89
G932
Speed control gain (Advanced
magnetic flux vector)
0 to 200%, 9999
0.1%
9999
90
C120
Motor constant (R1)
0 to 50
Ω
0.001
Ω
9999
0 to 400 m
Ω
, 9999
0.01 m
Ω
91
C121
Motor constant (R2)
0 to 50
Ω
0.001
Ω
9999
0 to 400 m
Ω
, 9999
0.01 m
Ω
92
C122
Motor constant (L1)/d-axis
inductance (Ld)
0 to 6000 mH, 9999
0.1 mH
9999
0 to 400 mH, 9999
93
C123
Motor constant (L2)/q-axis
inductance (Lq)
0 to 6000 mH, 9999
0.1 mH
9999
0 to 400 mH, 9999
94
C124
Motor constant (X)
0 to 100%, 9999
0.1%
9999
0.01%
95
C111
Online auto tuning selection
0 to 2
1
0
96
C110
Auto tuning setting/status
0, 1, 11, 101
1
0
Adjustabl
e
5 points
V/
F
100
G040
V/F1 (first frequency)
0 to 590 Hz, 9999
0.01 Hz
9999
101
G041
V/F1 (first frequency voltage)
0 to 1000 V
0.1 V
0 V
102
G042
V/F2 (second frequency)
0 to 590 Hz, 9999
0.01 Hz
9999
103
G043
V/F2 (second frequency voltage)
0 to 1000 V
0.1 V
0 V
104
G044
V/F3 (third frequency)
0 to 590 Hz, 9999
0.01 Hz
9999
105
G045
V/F3 (third frequency voltage)
0 to 1000 V
0.1 V
0 V
106
G046
V/F4 (fourth frequency)
0 to 590 Hz, 9999
0.01 Hz
9999
107
G047
V/F4 (fourth frequency voltage)
0 to 1000 V
0.1 V
0 V
108
G048
V/F5 (fifth frequency)
0 to 590 Hz, 9999
0.01 Hz
9999
109
G049
V/F5 (fifth frequency voltage)
0 to 1000 V
0.1 V
0 V
Th
ir
d
f
u
nct
ion
s
110
F030
Third acceleration/deceleration
time
0 to 3600 s, 9999
0.1 s
9999
111
F031
Third deceleration time
0 to 3600 s, 9999
0.1 s
9999
112
G020
Third torque boost
0 to 30%, 9999
0.1%
9999
113
G021
Third V/F (base frequency)
0 to 590 Hz, 9999
0.01 Hz
9999
114
H602
Third stall prevention operation
level
0 to 400%
0.1%
150%
115
H603
Third stall prevention operation
frequency
0 to 590 Hz
0.01 Hz
0 Hz
116
M445
Third output frequency detection
0 to 590 Hz
0.01 Hz
60 Hz
Functio
n
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value
Refer
to
page
Customer
settin
g
Содержание 800 Series
Страница 11: ...MEMO 10 ...
Страница 17: ...MEMO 16 ...
Страница 95: ...MEMO 94 ...
Страница 671: ...MEMO 670 ...
Страница 681: ...MEMO 680 ...