(G) Control parameters
595
5
GROUP
G
5.16.4
Excitation current low-speed scaling factor
Under Advanced magnetic flux vector control or Real sensorless vector control, the excitation current scaling factor in the low-
speed range can be adjusted.
The setting is valid only under Advanced magnetic flux vector control or Real sensorless vector control. When
Pr.14
= "12 to 15" and V/F control
is selected, the operation is the same as the one for constant-torque load (
Pr.14
= "0"). (Refer to
• Under Advanced magnetic flux vector control or Real sensorless vector control, excitation current in the low-speed range
can be increased to improve torque. When
Pr.14
= "12 to 15", the excitation current scaling factor can be switched for the
forward/reverse rotation.
• Increased excitation is applied when the output frequency is equal to or lower than the setting in
Pr.85 Excitation current
refraction point
. The excitation current scaling factor at 0 Hz is set in
Pr.86 Excitation current low speed multiplying
factor
. Use
Pr.565 Second motor excitation current refraction point and Pr.566 Second motor excitation current low
speed scaling factor
for the setting for using the second motor (RT signal-ON).
Pr.
Name
Initial
value
Setting
range
Description
14
G003
Load pattern selection
0
0 to 5
Excitation current low-speed scaling factor:
Pr.86
Refer to
for details of the operation under V/F control.
12
Forward rotation excitation current low-speed scaling factor:
Pr.86
Reverse rotation excitation current low-speed scaling factor:
Pr.617
13
Forward rotation excitation current low-speed scaling factor:
Pr.617
Reverse rotation excitation current low-speed scaling factor:
Pr.86
14
Forward rotation excitation current low-speed scaling factor:
Pr.86
Reverse rotation excitation current low-speed scaling factor:
Pr.617
(X17-OFF),
Pr.86
(X17 signal-ON)
15
Forward rotation excitation current low-speed scaling factor:
Pr.617
(X17-OFF),
Pr.86
(X17 signal-ON)
Reverse rotation excitation current low-speed scaling factor:
Pr.86
85
G201
Excitation current
refraction point
9999
0 to 400 Hz
Set the frequency at which increased excitation is started.
9999
10 Hz is applied.
86
G202
Excitation current low
speed multiplying
factor
9999
0 to 300%
Set an excitation current scaling factor at 0 Hz.
9999
130% is applied.
617
G080
Reverse rotation
excitation current low-
speed scaling factor
9999
0 to 300%
Set an excitation current scaling factor when different excitation
current scaling factors are used for forward and reverse rotation.
9999
130% is applied.
565
G301
Second motor
excitation current
refraction point
9999
0 to 400 Hz
Set an excitation current break point when the RT signal is ON.
9999
10 Hz is applied.
566
G302
Second motor
excitation current low
speed scaling factor
9999
0 to 300%
Set an excitation current low-speed scaling factor when the RT
signal is ON.
9999
130% is applied.
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless
Excitation current scaling factor
100%
0
Output frequency
Pr.86
(Pr.566)
Pr.85
(Pr.565)