522
5.14.15
Offline auto tuning for a frequency search
For the FR-A860-01080
or lower.
For the FR-A860-01440
or higher.
During V/F control, the accuracy of the "frequency search", which is used to detect the motor speed for the automatic
restart after instantaneous power failure and flying start, can be improved.
Pr.
Name
Initial
value
Setting range
Description
162
A700
Automatic restart after
instantaneous power failure
selection
0
0, 1000
Frequency search only performed at the first start
1, 1001
Reduced voltage start only at the first start
(no frequency search)
2, 1002
Encoder detection frequency search
3, 1003
Frequency search only performed at the first start
(reduced impact restart)
10, 1010
Frequency search at every start
11, 1011
Reduced voltage start at every start (no frequency
search)
12, 1012
Encoder detection frequency search at every start
13, 1013
Frequency search at every start (reduced impact
restart)
298
A711
Frequency search gain
9999
0 to 32767
The offline auto tuning automatically sets the gain
required for the frequency search.
9999
Uses the constant value of standard motor.
560
A712
Second frequency search
gain
9999
0 to 32767
The offline auto tuning automatically sets the gain
required for the frequency search of the second
motor.
9999
Uses the constant value of standard motor.
96
C110
Auto tuning setting/status
0
0
No offline auto tuning.
1, 101
Perform offline auto tuning for the Advanced
magnetic flux vector control, Real sensorless vector
control, and vector control. (Refer to
11
Performs offline auto tuning without rotating the motor
(V/F control).
90
C120
Motor constant (R1)
9999
0 to 50
Ω
Tuning data
(The value measured by offline auto tuning is
automatically set.)
9999: Uses the constant value of standard motor.
0 to 400 m
Ω
, 9999
463
C210
Second motor auto tuning
setting/status
0
0
No auto tuning for the second motor.
1, 101
Performs offline auto tuning for the second motor.
11
Performs offline auto tuning without rotating the
second motor (V/F control).
458
C220
Second motor constant (R1)
9999
0 to 50
Ω
Tuning data of the second motor
(same as
Pr.90
)
0 to 400 m
Ω
, 9999
V/F
V/F
V/F
Содержание 800 Series
Страница 11: ...MEMO 10 ...
Страница 17: ...MEMO 16 ...
Страница 95: ...MEMO 94 ...
Страница 671: ...MEMO 670 ...
Страница 681: ...MEMO 680 ...