493
5
GROUP
A
When
Pr.133
"9999", the
Pr.133
setting is valid.
CC-Link, CC-Link IE Field Network, or LONWORKS communication is available. For details on communication, refer to the Instruction Manual of
each option.
For the details of the PLC function, refer to the PLC Function Programming Manual.
• The set point/deviation input method can also be flexibly selected by
Pr.609 PID set point/deviation input selection
and
the measured value input method can be selected by
Pr.610 PID measured value input selection
. Selection by
Pr.609
and Pr.610
is valid when
Pr.128
= "1000 to 2011".
When the same input method has been selected for the set point and measured value using
Pr.609
and
Pr.610
, set point input is invalid. (The
inverter runs at set point 0%)
CC-Link, CC-Link IE Field Network, or LONWORKS communication is available. For details on communication, refer to the Instruction Manual of
each option.
NOTE
• When terminals 2 and 4 are selected for deviation input, perform bias calibration using
C3
and
C6
to prevent a minus voltage
from being entered as the deviation input signal. Input of a minus voltage might damage devices and the inverter.
• For the set point setting by parameters, the set point setting screen can be displayed quickly by setting the Extended direct
setting. (Refer to
.)
• The following shows the relationship between the input values of the analog input terminals and set point, measured value
and deviation. (Calibration parameter initial values)
Can be changed by
Pr.73 and Pr.267
and the voltage/current input switch. (Refer to
.)
NOTE
• Always perform calibration after changing the voltage/input specification with
Pr.73
,
Pr.267
, and the voltage/current input
selection switch.
1000
Valid
Reverse action
According to
Pr.609
According to
Pr.610
-
1001
Forward action
1010
Reverse action
-
-
According to
Pr.609
1011
Forward action
2000
Reverse action (without
frequency reflected)
According to
Pr.609
According to
Pr.610
-
2001
Forward action (without
frequency reflected)
2010
Reverse action (without
frequency reflected)
-
--
According to
Pr.609
2011
Forward action (without
frequency reflected)
Pr.609 and Pr.610 settings
Input method
1
Terminal 1
2
Terminal 2
3
Terminal 4
4
Communication
5
PLC function
Input
terminal
Inspect
specification
Relationship with analog input
Calibration parameter
Set point
Result
Deviation
Terminal 2
0 to 5 V
0 V=0%
5 V=100%
0 V=0%
5 V=100%
0 V=0%
5 V=100%
Pr.125, C2 to C4
0 to 10 V
0 V=0%
10 V=100%
0 V=0%
10 V=100%
0 V=0%
10 V=100%
0 to 20 mA
0 mA=0%
20 mA=100%
0 mA=0%
20 mA=100%
0 V=0%
20 mA=100%
Terminal 1
0 to
5 V
-5 V to 0 V=0%
5 V=+100%
-5 V to 0 V=0%
5 V=+100%
-5 V=-100%
0 V=0%
5 V=+100%
When
Pr.128
= "10",
Pr.125, C2 to C4.
When
Pr.128
"1000",
C12 to C15.
0 to
10 V
-10 V to 0 V=0%
10 V=+100%
-10 V to 0 V=0%
10 V=+100%
-10 V=-100%
0 V=0%
10 V=+100%
Terminal 4
0 to 5 V
0 V to 1 V=0%
5 V=100%
0 Vto 1 V=0%
5 V=100%
0 V=-20%
1 V=0%
5 V=100%
Pr.126, C5 to C7
0 to 10 V
0 V to 2 V=0%
10 V=100%
0 V to 2 V=0%
10 V=100%
0 V=-20%
1 V=0%
10 V=100%
0 to 20 mA
0 to 4 mA=0%
20 mA=100%
0 to 4 mA=0%
20 mA=100%
0 V=-20%
4 mA=0%
20 mA=100%
Pr.128
setting
Pr.609
Pr.610
PID action
Set point input
Measured value input
Deviation input