Position control under vector control
231
5
Cumulative pulse monitor value clear (Pr.635)
• The cumulative pulse monitor and the cumulative pulse overflow times can be cleared by X52 signal or X53 signal.
• To input the X52 or X53 signal, set "52 (X52)" or "53 (X53)" in any of
Pr.178 to Pr.184 (Input terminal function selection)
to assign the function to a terminal.
• Use
Pr.635 Cumulative pulse clear signal selection
to select the clearing method for the cumulative pulse monitor and
the cumulative pulse overflow times.
Cumulative pulse storage
• The cumulative pulse monitor value can be retained when the power is turned OFF or the inverter is reset.
NOTE
• When the power is turned OFF during the reset process, the cumulative pulse monitor value and the cumulative pulse
overflow times are not stored in the EEPROM.
• For storing the cumulative pulse monitor value and the cumulative pulse overflow times, in the EEPROM at power OFF,
connect R1/L11 with P/+, and S1/L21 with N/- so that the control power is retained. When connecting the converter unit (FR-
CC2), assign the instantaneous power failure detection (X11) signal to an input terminal to input the IPF signal from the FR-
CC2 to the terminal for X11 signal.
???????
Parameters referred to
Pr.52 Operation panel main monitor selection
Pr.635
setting
X52 signal
Cumulative pulse monitor clear
X53 signal
Cumulative pulse monitor clear (control terminal option)
0
Cleared at the edge when the signal is switched to ON.
Cleared at the edge when the signal is switched to ON.
1
Cleared while the signal is ON.
Cleared at the edge when the signal is switched to ON.
2
Cleared at the edge when the signal is switched to ON.
Cleared while the signal is ON.
3
Cleared while the signal is ON.
Cleared while the signal is ON.
Pr.638
setting
Cumulative pulse monitor/
cumulative pulse overflow times
Cumulative pulse monitor/
cumulative pulse overflow times
(control terminal option)
At power-OFF
At reset
At power-OFF
At reset
0
Not stored in the EEPROM
Cleared
Not stored in the EEPROM
Cleared
1
Stored in the EEPROM
Retained
Not stored in the EEPROM
Cleared
2
Not stored in the EEPROM
Cleared
Stored in the EEPROM
Retained
3
Stored in the EEPROM
Retained
Stored in the EEPROM
Retained
Clear signal
(X52, X53)
Cleared at the ON edge
Cleared while the signal is ON
Cumulative pulse
Cumulative pulse
overflow times
Clear signal
(X52, X53)
Cumulative pulse
Cumulative pulse
overflow times
ON
ON