(T) Multi-Function Input Terminal Parameters
400
5.12.4
Analog input responsiveness and noise
elimination
Block diagram
The frequency command/torque command responsiveness and stability are adjustable by using the analog input
(terminals 1, 2, and 4) signal.
Pr.
Name
Initial value
Setting range
Description
74
T002
Input filter time constant
1
0 to 8
The primary delay filter time constant to
the analog input is selectable. The higher
the value, the lower the responsiveness.
822
T003
Speed setting filter 1
9999
0 to 5 s
Set the primary delay filter time constant
to the external speed command (analog
input command).
9999
Use the
Pr.74
setting.
826
T004
Torque setting filter 1
9999
0 to 5 s
Set the primary delay filter time constant
to the external torque command (analog
input command).
9999
Use the
Pr.74
setting.
832
T005
Speed setting filter 2
9999
0 to 5 s, 9999
Second function of
Pr.822
(enabled when
the RT signal is ON)
836
T006
Torque setting filter 2
9999
0 to 5 s, 9999
Second function of
Pr.826
(enabled when
the RT signal is ON)
849
T007
Analog input offset
adjustment
100%
0 to 200%
Make the analog speed input (terminal 2)
have an offset. This prevents the motor
from rotating by noise to the analog input
or another cause on the speed 0
command.
Pr.836
Speed command
Pr.822
= 9999
Pr.822
9999
Pr.826
= 9999
Pr.826
Pr.74
Torque command
Pr.822
Pr.74
Pr.826
9999
Pr.832
9999
Pr.836
= 9999
Terminal 1 (2, 4) input
RT-OFF
RT-ON
Pr.832
= 9999
Pr.836
9999
Pr.832
Содержание 800 Series