(M) Monitor display and monitor output signal
388
5.11.12
Fault code output selection
• Fault codes can be output to the output terminals by setting
Pr.76
Fault code output selection
= "1 or 2".
• When the setting is "2", a fault code is only output when a fault occurs. In normal operation the terminal outputs the signal
assigned in
Pr.191 to Pr.194 (Output terminal function selection)
.
• The fault codes that can be output are shown in the table below. (0: Output transistor OFF, 1: Output transistor ON)
NOTE
• If an error occurs while
Pr.76
≠
"0", the output terminals SU, IPF, OL, and FU output the signals in the table above regardless
of the settings in
Pr.191 to Pr.194 (Output terminal function selection)
. Take caution when controlling the inverter with the
output signals set by
Pr.191 to Pr.194
.
???????
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)
When a fault occurs, the corresponding data can be output as a 4-bit digital signal using via an open collector output
terminal.
The fault code can be read using an input module of programmable controller, etc.
Pr.
Name
Initial value
Setting range
Description
76
M510
Fault code output selection
0
0
Without fault code output
1
With fault code output
(Refer to the table below.)
2
Fault code is output only when a fault occurs.
(Refer to the table below.)
Fault indication
Output terminal operation
Fault code
SU
IPF
OL
FU
Normal
0
0
0
0
0
E.OC1
0
0
0
1
1
E.OC2
0
0
1
0
2
E.OC3
0
0
1
1
3
E.OV1 to E.OV3
0
1
0
0
4
E.THM
0
1
0
1
5
E.THT
0
1
1
0
6
E.IPF
0
1
1
1
7
E.UVT
1
0
0
0
8
E.FIN
1
0
0
1
9
E.BE
1
0
1
0
A
E. GF
1
0
1
1
B
E.OHT
1
1
0
0
C
E.OLT
1
1
0
1
D
E.OPT
E.OP1 to E.OP3
1
1
1
0
E
Other than the above
1
1
1
1
F
When
Pr.76
= "2", the terminal outputs the signal assigned by
Pr.191 to Pr.194
.