(E) Environment setting parameters
249
5
GROUP
E
5.7.7
Resetting USB host errors
• Parameter copy and the trace function can be used when a USB device (such as a USB memory) is connected to the USB
connector (connector A). (Refer to
• When a device such as a USB charger is connected to the USB connector and an excessive current (500 mA or higher)
flows, USB host error (UF warning) is displayed on the operation panel.
• If a UF warning occurs, disconnect the USB device and set
Pr.1049
="1" to cancel the USB error. (The UF warning can also
be canceled by resetting the inverter power or resetting with the RES signal.)
5.7.8
Multiple rating setting
Overload current rating and surrounding air temperature
• The overload current rating of the inverter can be changed by the
Pr.570
setting.
30°C for the FR-A860-00090 or lower.
Changing the parameter initial values and setting ranges
• When inverter reset and all parameter clear are performed after setting
Pr.570
, the parameter initial values are changed
according to each rating, as shown below.
When a USB device is connected to the USB connector (connector A), the USB host error can be canceled without
performing an inverter reset.
Pr.
Name
Initial value
Setting range
Description
1049
E110
USB host reset
0
0
Read only
1
Resets the USB host.
Four rating types of different rated current and permissible load can be selected. The optimal inverter rating can be
chosen in accordance with the application, enabling equipment size to be reduced.
Pr.
Name
Initial value
Setting
range
Description
570
E301
Multiple rating setting
2
0
SLD rating
1
LD rating
2
ND rating
3
HD rating
Pr.570
setting
Rating
Overload current rating
Surrounding air temperature
FR-A860-01080 or lower FR-A860-01440 or higher
0
SLD
110% 60 s, 120% 3 s (inverse-time characteristics)
40°C
40°C
1
LD
120% 60 s, 150% 3 s (inverse-time characteristics)
40°C
50°C
2
ND
150% 60 s, 200% 3 s (inverse-time characteristics)
40°C
50°C
3
HD
200% 60 s, 250% 3 s, 280% 0.5 s (inverse-time
characteristics)
40°C
40°C
Pr.
Name
Pr.570 setting
Refer
to page
0
1
2
(Initial value)
3
0
Torque boost
7
Acceleration time
8
Deceleration time
9
Electronic thermal O/L relay
SLD rated
current
LD rated
current
ND rated
current
HD rated
current
22
Stall prevention operation level
110%
120%
150%
200%
,
48
Second stall prevention operation level
110%
120%
150%
200%
56
Current monitoring reference
SLD rated
current
LD rated
current
ND rated
current
HD rated
current
114
Third stall prevention operation level
110%
120%
150%
200%
148
Stall prevention level at 0 V input
110%
120%
150%
200%
149
Stall prevention level at 10 V input
120%
150%
200%
250%