Parameter List
Parameter list (by parameter number)
105
Pr.
List
5
RS-485
communic
a
tion
331
N030
RS-485 communication station
number
0 to 31 (0 to 247)
1
0
332
N031
RS-485 communication speed
3, 6, 12, 24, 48, 96,
192, 384, 576, 768,
1152
1
96
333
-
RS-485 communication stop bit
length / data length
0, 1, 10, 11
1
1
N032
PU communication data length
0, 1
1
0
N033
PU communication stop bit length
0, 1
1
1
334
N034
RS-485 communication parity
check selection
0 to 2
1
2
335
N035
RS-485 communication retry count
0 to 10, 9999
1
1
336
N036
RS-485 communication check time
interval
0 to 999.8 s, 9999
0.1 s
0 s
337
N037
RS-485 communication waiting
time setting
0 to 150 ms, 9999
1 ms
9999
338
D010
Communication operation
command source
0, 1
1
0
339
D011
Communication speed command
source
0 to 2
1
0
340
D001
Communication startup mode
selection
0 to 2, 10, 12
1
0
341
N038
RS-485 communication CR/LF
selection
0 to 2
1
1
342
N001
Communication EEPROM write
selection
0, 1
1
0
343
N080
Communication error count
-
1
0
Orien
tat
io
n co
nt
rol
349
—
Communication reset selection/
Ready bit status selection
0, 1, 100, 101
1
0
N010
Communication reset selection
0, 1
1
0
N240
Ready bit status selection
0, 1
1
0
350
A510
Stop position command selection
0, 1, 9999
1
9999
351
A526
Orientation speed
0 to 30 Hz
0.01 Hz
2 Hz
352
A527
Creep speed
0 to 10 Hz
0.01 Hz
0.5 Hz
353
A528
Creep switchover position
0 to 16383
1
511
354
A529
Position loop switchover position
0 to 8191
1
96
355
A530
DC injection brake start position
0 to 255
1
5
356
A531
Internal stop position command
0 to 16383
1
0
357
A532
Orientation in-position zone
0 to 255
1
5
358
A533
Servo torque selection
0 to 13
1
1
359
C141
Encoder rotation direction
0, 1, 100, 101
1
1
,
360
A511
16-bit data selection
0 to 127
1
0
361
A512
Position shift
0 to 16383
1
0
362
A520
Orientation position loop gain
0.1 to 100
0.1
1
363
A521
Completion signal output delay
time
0 to 5 s
0.1 s
0.5 s
364
A522
Encoder stop check time
0 to 5 s
0.1 s
0.5 s
365
A523
Orientation limit
0 to 60 s, 9999
1 s
9999
366
A524
Recheck time
0 to 5 s, 9999
0.1 s
9999
Encode
r feedba
ck
367
G240
Speed feedback range
0 to 590 Hz, 9999
0.01 Hz
9999
368
G241
Feedback gain
0 to 100
0.1
1
369
C140
Number of encoder pulses
0 to 4096
1
1024
,
374
H800
Overspeed detection level
0 to 590 Hz, 9999
0.01 Hz
9999
376
C148
Encoder signal loss detection
enable/disable selection
0, 1
1
0
Functio
n
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value
Refer
to
page
Customer
settin
g