Speed control under Real sensorless vector control, vector control, PM sensorless vector
control
161
5
Changing the setting increments of the torque limit level (Pr.811)
• The setting increments of
Pr.22
Torque limit level
,
Pr.801
Output limit level
, and
Pr.812
to
Pr.817
Torque limit level can
be changed to 0.01% by setting
Pr.811
Set resolution switchover
= "10 or 11".
For the details of the increments of speed setting and running speed monitoring, refer to
NOTE
• The internal resolution of the torque limit is 0.024% (100/2
12
), and fractions below this resolution are rounded off.
• When Real sensorless vector control is selected, fractions below a resolution equivalent to 0.1% are rounded off even if
Pr.811
="10, 11" is set.
• For details on changing the speed setting increments, refer to
Changing the torque characteristic of the constant-power range (Pr.801,
Pr.803)
• Under Real sensorless vector control or Vector control, the torque characteristic can be changed between in the low-speed
range and in the constant power range.
• Use
Pr.85
Excitation current refraction point
to change the low-speed range, and use
Pr.86
Excitation current low
speed multiplying factor
to change the torque in the low-speed range. When
Pr.85
= "9999 (initial value)", a
predetermined frequency is used. When
Pr.86
= "9999 (initial value)", a predetermined scaling factor is used (refer to
).
This is applicable only under Real sensorless vector control. The upper limit of the torque at 0 Hz is determined by multiplying the torque limit in
the constant-torque range by the scaling factor set in
Pr.86
.
• To avoid overload or overcurrent of the inverter or motor, use
Pr.801 Output limit level
to limit the torque current.
Pr.811
setting
Increments of speed setting and running
speed monitoring
Torque limit setting increments
0
1 r/min
0.1%
1
0.1 r/min
10
1 r/min
0.01%
11
0.1 r/min
Pr.803 setting
Torque characteristic in low-
speed range
Torque characteristic in constant-power range
Torque characteristic
Output limit
0 (initial value)
The torque changes according to
the scaling factor set in
Pr.86
.
Constant motor output
—
1
Constant torque
Constant torque
Without
2
Constant torque
Constant torque
With
10
Constant torque
Constant motor output
—
11
The torque changes according to
the scaling factor set in
Pr.86
.
Constant torque
Without
Pr.801 setting
Description
0 to 400%
Set the torque current limit level.
9999
The torque limit setting value (
Pr.22, Pr.812 to Pr.817
, etc.) is used for limiting the torque current.
Pr.85
Pr.803
=0
Torque
Low-speed
range
Constant torque
range
Constant power range
Constant power limit
Torque rise limit
Rated speed
Speed
Pr.803
=1
Constant torque limit
Constant torque limit
Pr.85
Rated speed
Speed
Torque
Low-speed
range
Constant torque
range
Constant power range