(G) Control parameters
608
5.16.10
Regenerative brake selection and DC feeding
mode
The initial value or setting range for the standard model
The initial value or setting range for the separated converter type
Available only with the standard model
Details of the setting value
• FR-A860-01080 or lower
• FR-A860-01440 or higher
• FR-A862-05450 or higher
For the FR-A860-00170 or lower.
For the FR-A860-00320 or higher.
For the FR-A860-00090 or lower.
While the power is supplied only to the control circuit with
Pr.30
= "100 or higher", the inverter reset is not performed when the power is supplied to the
main circuit.
• When performing frequent start and stop operation, usage rate of the regenerative brake can be increased by using
the brake resistor or the brake unit.
• It is possible to choose between the DC feeding mode 1, which will operate with DC power supply (terminals P and
N), and DC feeding mode 2, which will normally operate in AC power supply (terminals R, S, and T) and operate in
DC power supply (terminal P and N), such as batteries, at the time of power failure.
• While the power is supplied only to the control circuit, the reset operation when the power is supplied to the main
circuit can be selected.
Pr.
Name
Initial
value
Setting range
Description
30
E300
Regenerative
function selection
0
10
0 to 2, 10, 11, 20,
21, 100 to 102,
110, 111, 120,
121
Set the applied regeneration unit, the terminal used for power
supply, and whether to reset the inverter when the power is
supplied to the main circuit.
2, 10, 11, 102,
110, 111
70
G107
Special regenerative
brake duty
0%
0 to 100%
Set the %ED of the built-in brake transistor operation.
599
T721
X10 terminal input
selection
0
1
0
Normally open input
1
Normally closed input (NC contact input specification)
Regeneration unit
Power supply
terminals of inverter
Pr.30
Pr.70
Setting
Remarks
,
Brake unit
R, S, T
0 (initial
value), 100
―
The regenerative brake duty will be as follows.
• FR-A860-00090 or lower: 2%
• Other than above: 0%
P, N
10, 110
R, S, T/P, N
20, 120
Brake resistor other than the
provided brake resistor
R, S, T
1, 101
6%
―
P, N
11, 111
R, S, T/P, N
21, 121
For manufacturer's. Do not set.
―
2, 102
―
―
Regeneration unit
Power supply
terminals of inverter
Pr.30 Setting
Pr.70 Setting
Without regenerative function
R, S, T
0 (initial value), 100
―
P, N
10, 110
R, S, T/P, N
20, 120
For manufacturer's. Do not set.
―
1, 2, 11, 21, 101, 102,
111, 121
0% (initial value)
Regeneration unit
Pr.30 Setting
Without regenerative function (FR-CC2) 10 (initial value), 110
For manufacturer's. Do not set.
2, 11, 102, 111