1
BCN-C22005-925
FR-A800 Series
Instruction Manual Supplement
1
Cooling fan operation selection during the test
operation
The cooling fan can be stopped during Vector control test operation or PM sensorless vector control test operation.
Cooling fan operation selection during the test operation (P.H106)
• When
P.H106
= "1" or
Pr.244
= "1000, 1001, or 1101 to 1105", the cooling fan can be set to always OFF during Vector control
test operation or PM sensorless vector control test operation.
Pr.
Name
Initial
value
Setting
range
Description
244
Cooling fan
operation selection
1
0
Cooling fan ON/OFF control is disabled. (The cooling fan is always
ON at power ON)
The cooling fan operates at power ON.
1
Cooling fan ON/OFF control is enabled.
The fan is always ON while the inverter is running. During a stop,
the inverter status is monitored and the fan switches ON/OFF
according to the temperature.
101 to 105
Cooling fan ON/OFF control is enabled.
Set the cooling fan stop waiting time within 1 to 5 seconds.
1000
Cooling fan ON/OFF control is disabled.
(The cooling fan is always ON at power
ON)
The cooling fan operates at power ON.
The cooling fan can
be set to always OFF
during Vector control
test operation or PM
sensorless vector
control test
operation.
1001
Cooling fan ON/OFF control is enabled.
The fan is always ON while the inverter is
running. During a stop, the inverter status
is monitored and the fan switches ON/OFF
according to the temperature.
1101 to
1105
Cooling fan ON/OFF control is enabled.
Set the cooling fan stop waiting time within
1 to 5 seconds.
H100
Cooling fan
operation selection
1
0
Cooling fan ON/OFF control is disabled. (The cooling fan is always
ON at power ON)
The cooling fan operates at power ON.
1
Cooling fan ON/OFF control is enabled.
The fan is always ON while the inverter is running. During a stop,
the inverter status is monitored and the fan switches ON/OFF
according to the temperature.
101 to 105
Cooling fan ON/OFF control is enabled.
Set the cooling fan stop waiting time within 1 to 5 seconds.
H106
Cooling fan
operation selection
during the test
operation
0
0
The cooling fan operates according to the
H100
setting during
Vector control test operation or PM sensorless vector control test
operation.
1
The cooling fan can be set to always OFF during Vector control test
operation or PM sensorless vector control test operation.