(M) Monitor display and monitor output signal
354
Monitoring cumulative energization time (Pr.563)
• When the cumulative energization time is selected as a monitor item (
Pr.52
= "20"), the counter of cumulative energization
time since the inverter shipment accumulated every hour is displayed.
• The cumulative energization time is displayed in 0.001-hour increments until the cumulative time reaches one hour, and
then the time is displayed in 1-hour increments.
• The EEPROM is updated every minute until the cumulative energization time reaches one hour, and then the EEPROM is
updated every 10 minutes. The EEPROM is also updated at power OFF.
• When the cumulative energization time counter reaches 65535, it starts from 0 again. The number of times the cumulative
energization time counter reaches 65535 can be checked with
Pr.563
.
NOTE
• The cumulative energization time does not increase if the power is turned OFF after less than an hour.
Actual operation time monitoring (Pr.171, Pr.564)
• On the actual operation time monitoring (
Pr.52
= "23"), the inverter running time is added up every hour. (Time is not added
up during a stop.)
• The time is displayed in 1-hour increments.
• The values are stored in EEPROM every 10 minutes. The EEPROM is also updated at power OFF.
• When the cumulative energization time counter reaches 65535, it starts from 0 again. The number of times the actual
operation time counter reaches 65535 can be checked with
Pr.564
.
• Setting "0" in
Pr.171
clears the actual operation time meter.
NOTE
• The actual operation time does not increase if the cumulative running time before power OFF is less than an hour.
• Once "0" is set in
Pr.171
, the setting of
Pr.171
is always turned to "9999" afterwards. Setting "9999" does not clear the actual
operation time meter.
Hiding the decimal places for the monitors (Pr.268)
• The numerical figures after a decimal point displayed on the operation panel may continuously fluctuate during analog
input, etc. The decimal places can be hidden by selecting the decimal digits with
Pr.268
.
NOTE
• The number of display digits on the cumulative energization time (
Pr.52
= "20"), actual operation time (
Pr.52
= "23"),
cumulative power (
Pr.52
= "25") and cumulative energy saving (
Pr.52
= "51") does not change.
Pr.268 setting
Description
9999 (initial value)
No function
0
For the first or second decimal places (0.1 increments or 0.01 increments) of the monitor, numbers in the first
decimal place and smaller are rounded to display an integral value (1 increments). The monitor value equal to or
smaller than 0.99 is displayed as 0.
1
When monitoring with the second decimal place (0.01 increments), the 0.01 decimal place is dropped and the
monitor displays the first decimal place (0.1 increments). When monitoring with the first decimal place, the display
will not change.