(E) Environment setting parameters
257
5
GROUP
E
• 3-line monitor setting
The 3-line monitor is used as the first monitor.
• Direct setting
Pressing the [FUNC] key of the FR-PU07-01 displays the direct setting screen. The PID action set point can be directly set
regardless of the operation mode or
Pr.77 Parameter write selection
setting.
Pressing the [FUNC] key on the direct setting screen displays the function menu.
• Dedicated parameter list function
Pressing the [PrSET] key of the FR-PU07-01 displays the dedicated parameter list. Parameters that need to be set first for
the PID extended display setting are listed.
NOTE
• The display of parameters other than the above may be changed due to changes in
Pr.934
or
Pr.935
. Set the PID monitor
indicator before changing the settings of other parameters.
• To use the direct setting on the LCD operation panel, set
Pr.1000 Direct setting selection
. (Refer to
GOT initial setting (PU connector) (Pr.999 = "10, 12")
When
Pr.414
="1", the setting value is not changed.
• Initial setting with the GOT2000 series
- When "FREQROL 500/700/800, SENSORLESS SERVO" is selected for "Controller Type" in the GOT setting, set
Pr.999
="10" to configure the GOT initial setting.
- When "FREQROL 800 (Automatic Negotiation)" is selected for "Controller Type" in the GOT setting, the GOT automatic
connection can be used. When "FREQROL 800 (Automatic Negotiation)" is selected for "Controller Type" in the GOT
setting and the GOT automatic connection is not used, set
Pr.999
="12" to configure the GOT initial setting. (Refer to
• Initial setting with the GOT1000 series
- Set
Pr.999
="10" to configure the GOT initial setting.
NOTE
• Always perform an inverter reset after the initial setting.
• For the details of connection with GOT, refer to the Instruction Manual of GOT.
Direct setting
Parameter to be set
Direct setting 1
Pr.133 PID action set point
Direct setting 2
Pr.755 Second PID action set point
Dedicated parameter list
Parameter to be set
No.1
Pr.999 Automatic parameter setting
No.2
Pr.934 PID display bias coefficient
No.3
Pr.935 PID display gain coefficient
Pr.
Name
Initial
value
Pr.999="10"
Pr.999="12"
Refer to page
79
Operation mode selection
0
1
1
118
PU communication speed
192
192
1152
119
PU communication stop bit length
1
10
0
120
PU communication parity check
2
1
1
121
Number of PU communication retries
1
9999
9999
122
PU communication check time interval
9999
9999
9999
123
PU communication waiting time setting
9999
0 ms
0 ms
124
PU communication CR/LF selection
1
1
1
340
Communication startup mode selection
0
0
0
414
PLC function operation selection
0
—
2