(N) Operation via communication and its settings
585
5
GROUP
N
5.15.8
Automatic connection with GOT
When
Pr.549 Protocol selection
= "1" (MODBUS RTU protocol), the setting range is as shown in the parentheses.
When the set value is outside of the setting range, the initial value is applied.
Automatic connection system configuration
GOT2000 series automatic recognition
• When the GOT2000 series is connected, the parameters required for the GOT connection are automatically changed by
setting the automatic recognition on the GOT2000 series side.
• Set the station number (
Pr.117
or
Pr.331
) of the inverter before the automatic recognition is performed.
• Connect all the stations of inverters with GOT before the automatic recognition is performed. The inverter newly added after
automatic recognition will not be recognized automatically. (When an inverter is added, perform the initial setting in
Pr.999
Automatic parameter setting
or set the automatic recognition on the GOT side again.)
NOTE
• If the automatic recognition cannot be performed, initial setting in
Pr.999
is required.
• For connection to a device other than the GOT2000 series, initial setting in
Pr.999
is required.
• For details, refer to the GOT2000 Series Connection Manual (Mitsubishi Electric Product).
Parameters referred to
Pr.999 Automatic parameter setting
When the automatic connection is enabled in the GOT2000 series, the inverter can communicate with the GOT2000
series with only setting the station number and connecting the GOT. This eliminates the need for the communication
parameter setting.
Pr.
Name
Initial
value
Setting
range
Description
117
N020
PU communication
station number
0
0 to 31
Set the inverter station numbers.
The inverter station number setting is required when multiple
inverters are connected to one GOT (PU connector
communication).
331
N030
RS-485 communication
station number
0
0 to 31
(0 to 247)
Set the inverter station numbers.
The inverter station number setting is required when multiple
inverters are connected to one GOT (RS-485 terminal
communication).
Automatic change item
Automatic change parameter
Setting value after
change
PU connector connection
RS-485 terminal connection
Communication speed
Pr.118
Pr.332
Depending on the setting
of the connected device
on the GOT side.
Data length/stop bit
Pr.119
Pr.333
Parity
Pr.120
Pr.334
Waiting time setting
Pr.123
Pr.337
CR/LF selection
Pr.124
Pr.341
Number of communication retries
Pr.121
Pr.335
9999 (fixed)
Communication check time interval
Pr.122
Pr.336
9999 (fixed)
Protocol selection
―
(
Pr.549
holds the value before
the automatic recognition.)
Pr.549
0 (fixed to Mitsubishi
inverter protocol)
GOT2000
Terminating resistor
Four-wire multidrop