494
Input/output signals
• Assigning the PID control valid terminal signal (X14) to the input terminal by
Pr.178 to Pr.189 (Input terminal function
selection)
enables PID control to be performed only when the X14 signal is turned ON. When the X14 signal is OFF,
regular inverter running is performed without PID action. (When the X14 signal is not assigned, PID control is enabled only
by setting
Pr.128
≠
"0".)
• Input signal
• Output signal
NOTE
• Changing the terminal functions with
Pr.178 to Pr.189 and Pr.190 to Pr.196
may affect other functions. Set parameters after
confirming the function of each terminal.
Signal
Function
Pr.178 to Pr.189
setting
Description
X14
PID control valid terminal
14
When the signal is assigned to the input terminal, PID control is enabled
when the signal is ON.
X80
Second PID control valid
terminal
80
X64
PID forward/reverse
action switchover
64
PID control is switched between forward and reverse action without
changing parameters by turning ON the signal.
X79
Second PID forward/
reverse action switchover
79
X72
PID P control switchover
72
Integral and differential values can be reset by turning the signal ON.
X73
Second PID P control
switchover
73
Signal
Function
Pr.190 to Pr.196
setting value
Description
positive
logic
negative
logic
FUP
PID upper limit
15
115
Output when the measured value signal exceeds
Pr.131 PID upper limit
(Pr.1143 Second PID upper limit)
.
FUP2
Second PID upper limit
201
301
FDN
PID lower limit
14
114
Output when the measured value signal falls below
Pr.132 PID lower
limit (Pr.1144 Second PID lower limit)
.
FDN2
Second PID lower limit
200
300
RL
PID forward/reverse
rotation output
16
116
"Hi" is output when the output display of the parameter unit is forward
rotation (FWD), and "Low" is output when the display is reverse rotation
(REV) and stop (STOP).
RL2
Second PID forward/
reverse rotation output
202
302
PID
During PID control
activated
47
147
Turns ON during PID control.
When the PID calculation result is reflected to the output frequency
(
Pr.128
< "2000"), the PID signal turns OFF at turn OFF of the start signal.
When the PID calculation result is not reflected to the output frequency
(
Pr.128
"2000"), the PID signal turns ON during PID calculation
regardless of the start signal status.
PID2
Second During PID
control activated
203
303
SLEEP
PID output interruption
70
170
Set
Pr.575 Output interruption detection time (Pr.1147 Second output
interruption detection time)
"9999". This signal turns ON when the
PID output suspension function is activated.
SLEEP2
During second PID output
shutoff
204
304