(M) Monitor display and monitor output signal
387
5
GROUP
M
• When
Pr.158 AM terminal function selection
= "87, 88, 89, or 90", an analog voltage can be output from the terminal AM.
• Terminal AM output [V] = 10 [V]
(analog remote output value - 1000)/100
The output range is -10 V to +10 V regardless of the
Pr.290 Monitor negative output selection
setting.
Analog remote output data retention (Pr.655)
NOTE
• When
Pr.655
= "1 or 11" (remote analog output data retention at power OFF), take measures such as connecting R1/L11 with
P/+, and S1/L21 with N/- so that the control power is retained (While power is supplied to R/L1, S/L2 and T/L3). If the control
power is not retained, the analog output after turning ON the power is not guaranteed to work. When connecting the converter
unit (FR-CC2), assign the instantaneous power failure detection (X11) signal to an input terminal to input the IPF signal from
the FR-CC2 to the terminal for X11 signal.
???????
Parameters referred to
Pr.54 FM terminal function selection
Pr.158 AM terminal function selection
Pr.290 Monitor negative output selection
Pr.291 Pulse train I/O selection
• When the power supply is reset (including a power failure)
while
Pr.655
Analog remote output selection
= "0" (initial
value) or 10" and , the remote analog output (
Pr.656 to
Pr.659
) returns to its initial value (1000%).
• When
Pr.655
= "1 or 11", the analog remote output data is
saved in EEPROM before the power supply is turned OFF.
This means that the analog value output after power
restoration is the same as before the power supply was
turned OFF. However, when
Pr.655
= "1", the data is not
saved during an inverter reset (terminal reset, reset request
via communication).
• When
Pr.655
= "10 or 11", the analog output before the reset
is saved even during an inverter reset.
• When the setting in
Pr.655
is changed, the remote analog
output (
Pr.656 to Pr.659
) returns to its initial value (1000%).
10
1100
1200
-10
900
Output voltage [V]
800
1000
Analog remote output value [%]
Terminal AM
0
Power
supply
OFF
OFF
Power
supply
Analog
output
Analog output
clear
Analog
output
held
Inverter
reset time
(about 1s)
Pr.655
= 0, 10
Pr.655
= 1, 11
ON/OFF example for positive logic
Signal condition during a reset
Reset
ON
∗
Reset
ON
Pr.655
= 0, 1
Pr.655
= 10, 11
∗
When
Pr.655
= "1", the signal condition saved in EEPROM
(condition of the last power OFF) is applied.
Analog
output
saved
Analog
output
Analog
output
Analog
output