PRECAUTIONS FOR MAINTENANCE AND INSPECTION
Reinstallation (FR-A860-00061 to 02430)
1) After confirming the orientation of the fan, reinstall the fan so that the "AIR FLOW" faces up.
2) Reconnect the fan connectors.
3) Reinstall the fan cover.
NOTE
• Installing the fan in the opposite direction of air flow can cause the inverter life to be shorter.
• Prevent the cable from being caught when installing a fan.
• Switch the power OFF before replacing fans. Since the inverter circuits are charged with voltage even after power OFF,
replace fans only when the inverter cover is on the inverter to prevent an electric shock accident.
AIR FLOW
FR-A860-00061, 00090
FR-A860-00170, 00320
FR-A860-00450
FR-A860-00680, 01080
FR-A860-01440 to 02430
2. Insert hooks
until you hear
a click sound.
1. Insert hooks
into holes.
FR-A860-00061, 00090
2. Insert hooks
until you
hear a click
sound.
1. Insert hooks
into holes.
FR-A860-00170 to 00450
2. Insert hooks
until you
hear a click
sound.
1. Insert hooks
into holes.
FR-A860-00680 to 02430