(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
288
5.8.7
Lift operation (automatic acceleration/
deceleration)
The setting range for the FR-A860-01080 or lower.
The setting range for the FR-A860-01440 or higher.
Lift operation (Pr.292 = "5, 6")
• When
Pr.292 Automatic acceleration/deceleration
is set to "5" or "6", the lift operation is selected, and each setting is
changed, as shown in the table below.
• During power driving, sufficient torque is generated, and during regenerative driving and during driving with no load, the
torque boost setting is adjusted automatically so as not to activate the overcurrent protective function by overexcitation.
• If the lift has a load in which the rated current of the inverter is exceeded, the maximum torque may be insufficient.
For a lift without counterweight, setting
Pr.14 Load pattern selection
to "2 or 3" (for lift load) and setting
Pr.19 Base
frequency voltage
appropriately give the maximum torque a greater advantage than when selecting the lift operation.
NOTE
• The stall prevention operation level is automatically lowered according to the cumulative value of the electronic thermal O/L
relay so as to prevent an inverter overload trip (E.THT) and the motor overload trip (E.THM) from occurring.
The inverter can be operated according to the load pattern of the lift with counterweight.
Pr.
Name
Initial
value
Setting range
Description
292
F500
Automatic acceleration/
deceleration
0
0
Normal operation
1
Shortest acceleration/deceleration
(without brakes)
(Refer to
.)
11
Shortest acceleration/deceleration
(with brakes)
3
Optimum acceleration/deceleration
5
Lift operation 1 (stall prevention operation level
150%)
6
Lift operation 2 (stall prevention operation level
180%)
7, 8
Brake sequence 1, 2 (Refer to
.)
61
F510
Reference current
9999
0 to 500 A
Set the reference current during shortest (optimum)
acceleration/deceleration.
0 to 3600 A
9999
Rated output current value reference of the inverter
64
F520
Starting frequency for elevator
mode
9999
0 to 10 Hz
Set the starting frequency for the lift operation.
9999
Starting frequency is 2 Hz.
Name
Normal operation
Multi-rating
(Pr.570)
Lift operation (Pr.292)
5
6
Torque boost
Pr.0
(5/3/2/1%)
Changes according to the output current (as shown below)
Starting frequency
Pr.13
(0.5 Hz)
Pr.64
(2 Hz) Accelerate after 100 ms hold.
Base frequency voltage
Pr.19
(9999)
575 V
Stall prevention operation level
Pr.22
(150%), etc.
0 (SLD)
110%
115%
1 (LD)
120%
140%
2 (ND) Initial value
150%
180%
3 (HD)
200%
230%
V/F
V/F
V/F
6%
Pr.292
= "5"
Driving
current
(%)
When
Pr.0
=6%
Torque boost (%)
Regenerative
current
0
Pr.0
3%
100
115
Pr.292
= "6"
120 140
Torque boost 0%