Standard Inverter Specifications
9-
3
n
400-V
Class
Inverters
* For
applications of a NEMA1 mounting, remove the top and bottom covers and treat as IP00.
Table 9.2 Specifications for 400-V Class Inverters
Model
3G3RV-
A4004
A4007
A4015
A4022
A4037
A4040
A4055
A4075
A4110
A4150
A4185
Max.
applicable motor output (kW)
0.4
0.75
1.5
2.2
3.7
4
5.5
7.5
11
15
18.5
Output
specifi-
cations
Rated
output capacity
(kVA)
1.4
1.6
2.8
4
5.8
6.6
9.5
13
18
24
30
Rated
output current (A)
1.8
2.1
3.7
5.3
7.6
8.7
12.5
17
24
31
39
Max.
output voltage (V)
3-phase,
380 to 480 VAC (Depends on input voltage.)
Max.
output frequency (Hz)
CT
(low carrier, fixed torque applications): 150 Hz
VT
(high carrier, variable torque applications): 400 Hz
Power
supply
specifications
Rated
voltage (V)
Rated
frequency (Hz)
3-phase,
380 to 480 VAC 50/60 Hz
Allowable
voltage fluctua-
tion
-15%
to +10%
Allowable
frequency fluctu-
ation
±
5%
Power
supply capacity
(kVA)
1.7
1.9
3.3
4.9
6.9
7.9
12
15
22
28
36
Power
consumption (W)
53
58
84
115
148
148
209
307
410
498
634
Approx.
weight (kg)
3.0
3.0
3.0
4.0
4.0
4.0
4.0
6.0
6.0
10
10
Measures
for power supply harmonics
Optional
DC reactor
Protective
structure
Enclose,
wall-mounting (NEMA1: Equivalent to IP20) or Mounted in a panel (equivalent to IP00)
*
Model
3G3RV-
B4220
B4300
B4370
B4450
B4550
B4750
B4900
B411K
B413K
B416K
Max.
applicable motor output (kW)
22
30
37
45
55
75
90
110
132
160
Output
specifi-
cations
Rated
output capacity
(kVA)
34
46
57
69
85
110
140
160
200
230
Rated
output current (A)
45
60
75
91
112
150
180
216
260
304
Max.
output voltage (V)
3-phase,
380 to 480 VAC (Depends on input voltage.)
Max.
output frequency
(Hz)
CT
(low carrier, fixed torque applications): 150 Hz
VT
(high carrier, variable torque applications): 400 Hz
Power
supply
specifications
Rated
voltage (V)
Rated
frequency (Hz)
3-phase,
380 to 480 VAC 50/60 Hz
Allowable
voltage fluctua-
tion
-15%
to +10%
Allowable
frequency fluc-
tuation
±
5%
Power
supply capacity
(kVA)
38
52
63
76
91
125
151
181
217
254
Power
consumption (W)
725
995
1144
1316
1698
1974
2285
2950
3390
3938
Approx.
weight (kg)
21
21
36
36
36
88
89
102
120
160
Measures
for power supply harmonics
Built-in
DC reactor
Built-in
DC reactor
Protective
structure
Mounted
in a panel (equivalent to