5
-8
* 1. The
setting ranges for acceleration/deceleration times depends on the setting of C1-10 (Acceleration/deceleration Time Setting Unit). If C1-10 is set to
0,
the setting range is 0.00 to 600.00 (s).
* 2. The
factory setting depends on the Inverter capacity.
* 3. These
are values for a 200-V class Inverter. Values for a 400-V class Inverter are double.
* 4. The
upper setting limit will be 150.0 Hz when C6-01 is set to 0.
* 5. The
factory setting will change when the control method is changed. (V/f control factory settings are given.)
* 6. After
autotuning, E1-13 will contain the same value as E1-05.
* 7. The
factory setting depends on the Inverter capacity. (The value for a 200-V class Inverter for 0.4 kW is given.)
* 8. The
setting range is from 10% to 200% of the Inverter rated output current. (The value for a 200-V class Inverter for 0.4 kW is given.)
* 9. The
factory setting for (-E) models is 1024.
L3-04
Stall
pre-
vention
selection
during
deceleration
0: Disabled
(Deceleration as set. If
deceleration
time is too short, a
main
circuit overvoltage may
result.)
1: Enabled
(Deceleration is stopped
when
the main circuit voltage
exceeds
the overvoltage level.
Deceleration
restarts when voltage
is
returned.)
2: Intelligent
deceleration mode
(Deceleration
rate is automatically
adjusted
so that in Inverter can
decelerate
in the shortest possible
time.
Set deceleration time is
disregarded.)
3: Enabled
(with Braking Resistor
Unit)
When
a braking option (Braking
Resistor,
Braking Resistor Unit, Brak-
ing
Unit) is used, always set to 0 or 3.
0
to 3
1
No
Q
Q
Q
492H
StallP
Decel
Sel
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Regis-
ter
LCD
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor