Application
Settings
Parameters
are set as required in advanced programming mode (i.e., with the ADV indicator lit on the Digital
Operator).
All the parameters that can be set in quick programming mode can also be displayed and set in
advanced
programming mode.
n
Setting
Examples
The
following are examples of settings for applications.
•
When
using an Inverter-mounted Braking Resistor (3G3IV-PEPF
o
),
set L8-01 to 1 to enable Braking
Resistor
overheating protection.
•
To
prevent the machine from being operated in reverse, set b1-04 to 1 to disable reverse operation.
•
To
increase the speed of a 60 Hz motor by 10%, set E1-04 to 66.0 Hz.
•
To
use a 0 to 10-V analog signal for a 60 Hz motor for variable-speed operation between 0 and 54 Hz (0%
to
90% speed deduction), set H3-02 to 90.0%.
•
To
control speed between 20% and 80% to ensure smooth gear operation and limit the maximum speed of
the
machine, set d2-01 to 80.0% and set d2-02 to 20.0%.
K
K
K
K
No-load
Operation
To
start no-load operation (without connecting the machine to the motor), press the LOCAL/REMOTE Key
on
the Digital Operator to change to LOCAL mode (the SEQ and REF indicators on the Digital Operator
should
be OFF).
The
motor and the machine must be checked for safety before starting Inverter operation from the Digital
Operator.
Confirm that the motor works normally and that no errors are displayed at the Inverter.
Jog
Frequency Reference (d1-17, default: 6.00 Hz) can be started and stopped by pressing and releasing the
JOG
Key on the Digital Operator. If the external sequence prevent operation from the Digital Operator, con-
firm
that emergency stop circuits and machine safety mechanisms are functioning, and then start operation in
REMOTE
mode (i.e., with a signal from the control signal terminals). The safety precautions must always be
taken
before starting the Inverter with the motor connected to the machine.
K
K
K
K
Loaded
Operation
Connect
the machine to the motor and then start operation as described for no-load operation (i.e., from the
Digital
Operator or by using control circuit terminal signals).
n
Connecting
the
Load
•
After
confirming that the motor has stopped completely, connect the mechanical system.
•
Be
sure to tighten all the screws when securing the motor shaft to the mechanical system.
INFO
Both a RUN command (forward or reverse) and a frequency reference (or multi-step speed command) must
be provided to start Inverter operation.
Input these commands and reference regardless of the operation method (i.e., LOCAL of REMOTE).
Summary of Contents for SYSDRIVE 3G3RV
Page 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Page 36: ...1 22...
Page 106: ...3 14...
Page 126: ...4 20...
Page 216: ...5 90...
Page 388: ...7 26...