Wiring Control Circuit Terminals for European Models
2-
39
K
K
K
K
Control
Circuit
Terminal
Connections
Connections
to Inverter control circuit terminals are shown in Fig 2.30.
Fig 2.30 Control Circuit Terminal Connections (European (-E) Models)
MA
MB
MC
Fault contact output
250 VAC, 1 A max.
30 VDC, 1 A max.
M1
M2
Multi-function output
250 VAC, 1 A max.
30 VDC, 1 A max.
Default: Running signal
P
P
4 to 20 mA
0 to 10 V
Pulse train input
RP
+V
-V
A1
A2
AC
0 V
Master speed pulse train
0 to 32 kHz (3 kW)
High level: 3.5 to 13.2 V input
Frequency setting power
+15 V 20 mA
Frequency setting power
-15 V 20 mA
Master speed reference
0 to 10 V (20 kW)
Master speed reference
4 to 20 mA (250 W)
[0 to 10 V (20 kW) input]
Frequency setting
adjustment
Frequency
setter
2 k
External
frequency
references
2 k
2
1
3
IG
RS-485/422
communications
R-
R+
S-
S+
Terminating
resistance
AC
MP
Pulse train output
0 to 32 kHz (2.2 kW)
Default: Output frequency
S5
S6
S7
E(G)
Multi-step speed
setting 1
Multi-step speed
setting 2
Jog frequency selection
Shield terminal
S1
S2
S3
S4
Forward Run/Stop
Reverse Run/Stop
External fault
Fault reset
Multi-function
contact inputs
Defaults
Multi-function analog output 1
E(G)
-10 to 10 V 2 mA
AM
FM
Default: Output frequency
0 to +10 V
Default: Output current
0 to +10 V
-10 to 10 V 2 mA
Multi-function analog output 2
Ammeter adjustment
20 k
Ammeter adjustment
20 k
+24 V 8 mA
M3
M4
Multi-function output 1
250 VAC, 1 A max.
30 VDC, 1 A max.
(Default: Zero-speed)
M5
M6
Multi-function output 2
250 VAC, 1 A max.
30 VDC, 1 A max.
(Default: Frequency agree 1)
FM
AM
AC
CN15
V/I Converter
0 to 10V
/4 to 20mA
CN15
V/I Converter
0 to 10V
/4 to 20mA
SN
SP
SC
(PNP connection)
24V
+
-
* 1