10
-14
Parameters
Factory
settings are given in the following table. These settings are for a 200-V class Inverter of 0.4 kW
set
to factory set control method (open loop vector control).
Table 10.1 Parameters
No.
Name
Fac-
tory
Setting
Set-
ting
No.
Name
Fac-
tory
Setting
Set-
ting
A1-00
Language
selection for digital
operator
display
1
*1
b5-14
PID
feedback command loss detec-
tion
time
1.0
A1-01
Parameter
access level
2
b5-15
PID
sleep function operation level
0.0
A1-02
Control
method selection
0
*1
b5-16
PID
sleep operation delay time
0.0
A1-03
Initialize
0
b5-17
Acceleration/deceleration
time for
PID
reference
0.0
A1-04
Password
0
b5-18
PID
set point selection
0
A1-05
Password
setting
0
b5-19
PID
set point
0.0
A2-01
to
A2-32
User
setting parameters
-
b6-01
Dwell
frequency at start
0.0
b1-01
Reference
selection
1
b6-02
Dwell
time at start
0.0
b1-02
Operation
method selection
1
b6-03
Dwell
frequency at stop
0.0
b1-03
Stopping
method selection
0
b6-04
Dwell
time at stop
0.0
b1-04
Prohibition
of reverse operation
0
b8-01
Energy-saving
mode selection
0
b1-06
Read
sequence input twice
1
b8-02
Energy-saving
gain
0.7
*4
b1-07
Operation
selection after switching
to
remote mode
0
b8-03
Energy-saving
filter time constant
0.50
*5
b1-08
Run
command selection in pro-
gramming
modes
0
b8-04
Energy-saving
coefficient
*6
b2-01
Zero
speed level (DC injection
braking
starting frequency)
0.5
b8-05
Power
detection filter time con-
stant
20
b2-02
DC
injection braking current
50
b8-06
Search
operation voltage limiter
0
b2-03
DC
injection braking time at start
0.00
C1-01
Acceleration
time 1
10.0
b2-04
DC
injection braking time at stop
0.50
C1-02
Deceleration
time 1
10.0
b3-01
Speed
search selection
2
*2
*3
C1-03
Acceleration
time 2
10.0
b3-02
Speed
search operating current
120
*2
C1-04
Deceleration
time 2
10.0
b3-03
Speed
search deceleration time
2.0
C1-05
Acceleration
time 3
10.0
b3-05
Speed
search wait time
0.2
C1-06
Deceleration
time 3
10.0
b4-01
Timer
function ON-delay time
0.0
C1-07
Acceleration
time 4
10.0
b4-02
Timer
function OFF-delay time
0.0
C1-08
Deceleration
time 4
10.0
b5-01
PID
control mode selection
0
C1-09
Deceleration
stop time
10.0
b5-02
Proportional
gain (P)
1.00
C1-10
Accel/decel
time setting unit
1
b5-03
Integral
(I) time
1.0
C1-11
Accel/decel
time switching fre-
quency
0.0
b5-04
Integral
(I) limit
100.0
C2-01
S-curve
characteristic time at
acceleration
start
0.20
b5-05
Derivative
(D) time
0.00
C2-02
S-curve
characteristic time at
acceleration
end
0.20
b5-06
PID
limit
100.0
C2-03
S-curve
characteristic time at
deceleration
start
0.20
b5-07
PID
offset adjustment
0.0
C2-04
S-curve
characteristic time at
deceleration
end
0.00
b5-08
PID
primary delay time constant
0.00
C3-01
Slip
compensation gain
0.0
*3
b5-09
PID
output characteristics selec-
tion
0
C3-02
Slip
compensation primary delay
time
2000
*2
b5-10
PID
output gain
1.0
C3-03
Slip
compensation limit
200
b5-11
PID
reverse output selection
0
C3-04
Slip
compensation selection during
regeneration
0
b5-12
Selection
of PID feedback com-
mand
loss detection
0
C3-05
Output
voltage limit operation
selection
0
b5-13
PID
feedback command loss detec-
tion
level
0
C4-01
Torque
compensation gain
1.00