Maintenance and Inspection
8-
3
Periodic
inspection standards vary depending on the Inverter's installation environment and usage conditions.
The
Inverter's maintenance periods are noted below. Keep them as reference.
Note The
standard replacement period is based on the following usage conditions:
Ambient
temperature:Yearly average of 30
°
C
Load
factor: 80% max.
Operating
rate: 12 hours max. per day
Fig 8.2 Part Replacement Guidelines
Part
Standard Replacement Period
Replacement Method
Cooling
fan
2
to 3 years
Replace
with new part.
Smoothing
capacitor
5
years
Replace
with new part. (Determine need by
inspection.)
Breaker
relays
-
Determine
need by inspection.
Fuses
10
years
Replace
with new part.
Aluminum
capacitors on PCBs
5
years
Replace
with new board. (Determine need by
inspection.)