Input Terminal Functions
6-
71
n
Application
Precautions
•
Jog
frequencies using FJOG and RJOG commands are given priority over other frequency references.
•
When
both FJOG command and RJOG commands are ON for 500 ms or longer at the same time, the
Inverter
stops according to the setting in b1-03 (stopping method selection).
K
K
K
K
Stopping
the
Inverter
by
Notifying
Programming
Device
Errors
to
the
Inverter
(External
Error
Function)
The
external error function performs the error contact output, and stops the Inverter operation if the Inverter
peripheral
devices break down or an error occurs. The digital operator will display EFx (External error [input
terminal
Sx]). The x in EFx shows the terminal number of the terminal that input the external error signal. For
example,
if an external error signal is input to terminal S3, EF3 will be displayed.
To
use the external error function, set one of the values 20 to 2F in one of the parameters H1-01 to H1-05
(multi-function
contact input terminal S3 to S7 function selection).
Select
the value to be set in H1-01 to H1-05 from a combination of any of the following three conditions.
•
Signal
input level from peripheral devices
•
External
error detection method
•
Operation
during external error detection
The
following table shows the relationship between the combinations of conditions and the set value in H1-
oo
.
Note1.Set
the input level to detect errors using either signal ON or signal OFF. (NO contact: External error when ON; NC contact: External error when OFF).
2. Set
the detection method to detect errors using either constant detection or detection during operation.
Constant
detection: Detects while power is supplied to the Inverter.
Detection
during operation: Detects only during Inverter operation.
Set
Value
Input
Level
(See
Note
1.)
Error
Detection
Method
(See
Note
2.)
Operation
During
Error
Detection
NO
Contact
NC
Contact
Constant
Detection
Detection
During
Oper-
ation
Decelerate
to
Stop
(Error)
Coast
to
Stop
(Error)
Emergency
Stop
(Error)
Continue
Operation
(Warning)
20
Yes
Yes
Yes
21
Yes
Yes
Yes
22
Yes
Yes
Yes
23
Yes
Yes
Yes
24
Yes
Yes
Yes
25
Yes
Yes
Yes
26
Yes
Yes
Yes
27
Yes
Yes
Yes
28
Yes
Yes
Yes
29
Yes
Yes
Yes
2A
Yes
Yes
Yes
2B
Yes
Yes
Yes
2C
Yes
Yes
Yes
2D
Yes
Yes
Yes
2E
Yes
Yes
Yes
2F
Yes
Yes
Yes
Summary of Contents for SYSDRIVE 3G3RV
Page 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Page 36: ...1 22...
Page 106: ...3 14...
Page 126: ...4 20...
Page 216: ...5 90...
Page 388: ...7 26...