Parameter Tables
5-
53
* For
(-E) models. The shunt connector CN15 must be set. For details, refer to page 2-43.
n
RS-422A/485
Communications:
H5
Parameters
for RS-422A/485 communications are shown in the following table.
H4-08
Analog
out-
put
2 signal
level
selec-
tion
Sets
the signal output level
for
multi-function output 2
(terminal
AM)
0: 0
to +10 V output
1: 0
to ±10 V output
(2:
4 to 20 mA)
*
0
or 1
(0
to 2)
*
0
No
A
A
A
424H
6-72
AO
Level
Select2
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
H5-01
Slave
address
Set
the Inverter's slave
address.
0
to 20
*
1F
No
A
A
A
425H
6-76
Serial
Comm
Adr
H5-02
Communi-
cation
speed
selection
Set
the baud rate for 6CN
RS-422A/485
communica-
tions.
0: 1200
bps
1: 2400
bps
2: 4800
bps
3: 9600
bps
4: 19200
bps
0
to 4
3
No
A
A
A
426H
6-76
Serial
Baud
Rate
H5-03
Communi-
cation
parity
selection
Set
the parity for 6CN RS-
422A/485
communications.
0: No
parity
1: Even
parity
2: Odd
parity
0
to 2
0
No
A
A
A
427H
6-76
Serial
Com
Sel
H5-04
Stopping
method
after
com-
munication
error
Set
the stopping method for
RS-422A/485
communica-
tions
error.
0: Deceleration
to stop
using
deceleration time in
C1-02
1: Coast
to stop
2: Emergency
stop using
deceleration
time in C1-
09
3: Continue
operation
0
to 3
3
No
A
A
A
428H
6-76
Serial
Fault
Sel
H5-05
Communi-
cation
error
detection
selection
Set
whether or not a commu-
nications
timeout is to be
detected
as a communica-
tions
error (CE).
0: Do
not detect.
1: Detect
0
or 1
1
No
A
A
A
429H
6-76
Serial
Flt
Dtct
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register
Page
LCD
Display
V/f
V/f
with
PG
Open
Loop