Digital Operator Functions
6-
141
K
K
K
K
Prohibiting
Writing
Parameters
from
the
Digital
Operator
If
you set A1-01 to 0, you can refer to and set the A1 and A2 parameter groups, and refer to drive mode, using
the
Digital Operator.
If
you set one of the parameters H1-01 to H1-05 (multi-function contact input terminal S3 to S7 function
selection)
to 1B (write parameters permitted), you can write parameters from the digital operator when the ter-
minal
that has been set is ON. When the set terminal is OFF, writing parameters other than the frequency ref-
erence
is prohibited. You can, however, reference parameters.
n
Related
Parameters
K
K
K
K
Setting
a
Password
When
a password is set in A1-05, if the set values in A1-04 and A1-05 do not match, you cannot refer to or
change
the settings of parameters A1-01 to A1-03, or A2-01 to A2-32.
You
can prohibit the setting and referencing of all parameters except A1-00 by using the password function in
combination
with setting A1-01 to 0 (Monitor only).
n
Related
Parameters
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
A1-01
Parameter
access level
Used
to set the parameter access level (set/read.)
0:
Monitoring only (Monitoring drive mode and
setting
A1-01 and A1-04.)
1:
Used to select parameter
(Only
parameters set in A2-01 to A2-32 can
be
read and set.)
2:
ADVANCED
(Parameters
can be read and set in both quick
programming
mode and advanced program-
ming
(A) mode.)
0
to 2
2
Yes
A
A
A
Access
Level
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
A1-01
Parameter
access level
Used
to set the parameter access level (set/read.)
0:
Monitoring only (Monitoring drive mode and
setting
A1-01 and A1-04.)
1:
Used to select parameter
(Only
parameters set in A2-01 to A2-32 can
be
read and set.)
2:
ADVANCED
(Parameters
can be read and set in both quick
programming
mode and advanced program-
ming
(A) mode.)
0
to 2
2
Yes
A
A
A
Access
Level
A1-04
Password
Password
input when a password has been set in
A1-05.
This
function write-protects some parameters of
the
initialize mode.
If
the password is changed, A1-01 to A1-03 and
A2-01
to A2-32 parameters can no longer be
changed.
(Programming mode parameters can be
changed.)
0
to
9999
0
No
A
A
A
Enter
Password