This
section explains input terminal functions, which set operating methods by switching functions for the
multi-function
contact input terminals (S3 to S7).
K
K
K
K
Temporarily
Switching
Operation
between
Digital
Operator
and
Control
Circuit
Terminals
You
can switch the Inverter run command inputs and frequency reference inputs between local (i.e., Digital
Operator)
and remote (input method using b1-01 and b1-02).
You
can switch between local and remote by turning ON and OFF the terminals if an output from H1-01 to
H1-05
(multi-function input terminal S3 to S7 function selection) has been set to 1 (local/remote selection).
To
set the control circuit terminals to remote, set b1-01 and b1-02 to 1 (Control circuit terminals).
n
Related
Parameters
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
b1-01
Reference
selection
Set
the frequency reference input method.
0:
Digital Operator
1:
Control circuit terminal (analog input)
2:
RS-422A/485 communications
3:
Option Card
4:
Pulse input
0
to 4
1
No
Q
Q
Q
Reference
Source
b1-02
Operation
method selec-
tion
Set
the run command input method
0:
Digital Operator
1:
Control circuit terminal (sequence input)
2:
RS-422A/485 communications
3:
Option Card
0
to 3
1
No
Q
Q
Q
Run
Source
INFO
You can also perform local/remote switching using the LOCAL/REMOTE Key on the Digital Operator. When
the local/remote function has been set in the external terminals, the LOCAL/REMOTE Key function on the
Digital Operator will be disabled.