6
-14
Stopping
Methods
This
section explains methods of stopping the Inverter.
K
K
K
K
Selecting
the
Stopping
Method
There
are four methods of stopping the Inverter when a stop command is set:
•
Deceleration
to stop
•
Coast
to stop
•
DC
braking stop
•
Coast
to stop with timer
Set
parameter b1-03 to select the stopping method.
n
Related
Parameters
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
b1-03
Stopping
method selection
Sets
the stopping method when a stop command is
input.
0:
Deceleration to stop
1:
Coast to stop
2:
DC braking stop (Stops faster than coast to
stop,
without regenerative operation.)
3:
Coast to stop with timer (Run commands are
ignored
during deceleration time.)
0
to 3
0
No
Q
Q
Q
Stopping
Method
b2-01
Zero
speed level (DC
injection
braking starting
frequency)
Sets
the frequency to start the DC injection brak-
ing
in units of Hz when deceleration to stop is
selected.
DC
injection braking starts from E1-09 when b2-
01
< E1-09.
0.0
to
10.0
0.5
Hz
No
A
A
A
DCInj
Start Freq
b2-02
DC
injection braking cur-
rent
Sets
the DC injection braking current as a percent,
with
the Inverter rated current as 100%.
0
to
100
50%
No
A
A
A
DCInj
Current
b2-04
DC
injection braking time
at
stop
Sets
the DC injection braking time in seconds.
The
motor coasts to a stop after the deceleration
time
due to inertia. DC injection breaking stops
coasting.
The
value 0.00 disables DC injection.
0.00
to
10.00
0.50
s
No
A
A
A
DCInj
Time@Stop