Wiring Control Circuit Terminals for European Models
2-
43
n
Shunt
Connector
CN15
and
DIP
Switch
S1
The
shunt connector CN 15 and DIP switch S1 are described in this section.
Fig 2.32
Shunt Connector CN15 and DIP Switch S1
The
functions of DIP switch S1 are shown in the following table.
Table 2.22 DIP Switch S1
Name
Function
Setting
S1-1
RS-485
and RS-422A terminating resis-
tance
OFF:
No terminating resistance
ON:
Terminating resistance of 110
Ω
S1-2
Input
method for analog input A2
OFF:
0 to 10 V (internal resistance: 20 k
Ω
)
ON:
4 to 20 mA (internal resistance: 250
Ω
)
S1
O
F
F
1
2
CN15
Note: Refer to Table 2.13 for S1
functions
Current output
Voltage output (Factory setting)
Analog output switch
Terminating resistance
Analog input A2 swich
CN15
S1
: Factory settings
OFF
ON
V