9
-4
K
K
K
K
Common
Specifications
The
following specifications apply to both 200 V and 400 V Class Inverters.
Note Rotational
autotuning is required to obtain the specifications labeled as open loop vector control.
* 1. Not
including the 200 V Class Inverter for 110 kW and the 400 V Class Inverters for 220 and 300 kW.
* 2. Increase
the Inverter capacity if loads exceeding these current values are expected.
Table 9.3 Common Specifications
Model
Number
3G3RV-
o
o
o
o
Specification
Control
method
Sine
wave PWM
Open
loop vector control, V/f control, V/f with PG control (switched by parameter setting)
Speed
control range
1:100
(Open loop vector control)
Speed
control accuracy
±0.2%
(25
°
C
± 10
°
C)
(Open loop vector control)
Speed
control response
5
Hz (Open loop vector control)
Torque
characteristics
CT
selected (low carrier, fixed torque applications): 150% /0.5 Hz
VT
selected (high carrier, variable torque applications): 120%/0.5 Hz (Open loop vector control)
Torque
limits
Can
be set using parameter settings for open loop vector control only.
Frequency
control range
0.01
to 150 Hz (CT selected.), 0.01 to 400 Hz (VT selected.)
Frequency
accuracy (tem-
perature
characteristics)
Digital
references: ± 0.01% (-10
°
C
to +40
°
C)
Analog
references: ±0.1% (25
°
C
±10
°
C)
Frequency
setting resolu-
tion
Digital
references: 0.01 Hz
Analog
references: 0.06 Hz/60 Hz (10 bit with no sign)
Output
frequency resolu-
tion
0.001
Hz
Overload
capacity and
maximum
current
*2
CT
selected: 150% of rated output current per minute
*1
VT
selected: 120% of rated output current per minute
Frequency
setting signal
Voltage
input of 0 to
±
10
or 0 to 10 (20 k
Ω)
VDC or current input of 4 to 20 mA
Acceleration/Decelera-
tion
time
0.01
to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)
Braking
torque
Approximately
20% (Approximately 125% with Braking Resistor option
Main
control functions
Restarting
for momentary power loss, speed searches, overtorque detection, torque limits, 16-speed control (maximum), accelera-
tion/deceleration
time changes, S-curve acceleration/deceleration, 3-wire sequence, autotuning (rotational or stationary), dwell
functions,
cooling fan ON/OFF control, slip compensation, torque compensation, jump frequencies, upper and lower limits for
frequency
references, DC braking for starting and stopping, high-slip braking, PID control (with sleep function), energy-saving
control,
RS-485/422A communications (Conforms to MODBUS,19.2 kbps maximum), fault reset, and function copying.
Motor
protection
Protection
by electronic thermal overload relay.
Instantaneous
overcurrent
protection
Stops
at approx. 200% of rated output current.
Overload
protection
CT
selected (low carrier, fixed torque applications): 150% of rated output current per minute (except for 110 kW Inverters)
VT
selected (high carrier, variable torque applications): 120% of rated output current per minute
Overvoltage
protection
200
Class Inverter: Stops when main-circuit DC voltage is above 410 V.
400
Class Inverter: Stops when main-circuit DC voltage is above 820 V.
Undervoltage
protection
200
Class Inverter: Stops when main-circuit DC voltage is below 190 V.
400
Class Inverter: Stops when main-circuit DC voltage is below 380 V.
Momentary
power loss
ridethru
Stops
for 15 ms or more.
By
selecting the momentary power loss method, operation can be continued if power is restored within 2 s.
Cooling
fin overheating
Protection
by thermistor.
Grounding
protection
Protection
by electronic circuits. (Overcurrent level)
Charge
indicator
Lit
when the main circuit DC voltage is approx. 50 V or more.
Application
site
Indoor
(no corrosive gas, dust, etc.)
Ambient
operating tem-
perature
-10
°
C
to 40
°
C
(Closed wall-mounted type)
10
°
C
to 45
°
C
(Open chassis type)
Ambient
operating humid-
ity
95%
max. (with no condensation)
Storage
temperature
-
20
°
C
to + 60
°
C
(short-term temperature during transportation)
Altitude
1000
m max.
Insulation
resistance
5
MW max. (Do not perform insulation resistance with withstand voltage tests.)
Vibration
10
to 20 Hz, 9.8 m/s
2
max.; 20 to 50 Hz, 2 m/s
2
max, oscillation vibration of 20 Hz
Protective
structure
Enclose,
wall-mounting (NEMA1: Equivalent to IP20) or Mounted in a panel (equivalent to IP00)
Mounted
in a panel (equivalent to IP00)
Co
n
tr
o
l
ch
ar
act
er
is
ti
cs
Pr
o
te
ctiv
e
fu
nc
ti
o
ns
E
n
vi
ronm
en
t
Summary of Contents for SYSDRIVE 3G3RV
Page 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Page 36: ...1 22...
Page 106: ...3 14...
Page 126: ...4 20...
Page 216: ...5 90...
Page 388: ...7 26...