5
-60
* The
initial value when C6-01 is set to 1 is given. If C6-01 is set to 0, the initial value will be 150%.
L3-04
Stall
pre-
vention
selection
during
decel
0: Disabled
(Deceleration as
set.
If deceleration time is
too
short, a main circuit
overvoltage
may result.)
1: Enabled
(Deceleration is
stopped
when the main
circuit
voltage exceeds
the
overvoltage level.
Deceleration
restarts
when
voltage is returned.)
2: Intelligent
deceleration
mode
(Deceleration rate
is
automatically adjusted
so
that in Inverter can
decelerate
in the shortest
possible
time. Set
deceleration
time is
disregarded.)
3: Enabled
(with Braking
Resistor
Unit)
When
a braking option
(Braking
Resistor, Braking
Resistor
Unit, Braking Unit)
is
used, always set to 0 or 3.
0
to 3
1
No
Q
Q
Q
492H
4-8
6-25
StallP
Decel
Sel
L3-05
Stall
pre-
vention
selection
during
run-
ning
0: Disabled
(Runs as set.
With
a heavy load, the
motor
may stall.)
1: Deceleration
time 1 (the
deceleration
time for the
stall
prevention function
is
C1-02.)
2: Deceleration
time 2 (the
deceleration
time for the
stall
prevention function
is
C1-04.)
0
to 2
1
No
A
A
No
493H
6-42
StallP
Run
Sel
L3-06
Stall
pre-
vention
level
during
running
Effective
when L3-05 is 1 or
2.
Set
as a percentage of the
Inverter
rated current.
Usually
setting is not neces-
sary.
The
factory setting reduces
the
set values when the
motor
stalls.
30
to
200
120%
*
No
A
A
No
494H
6-42
StallP
Run
Level
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop