4
-14
n
Digital
Operator
Displays
during
Autotuning
The
following displays will appear on the Digital Operator during autotuning.
Table 4.5 Digital Operator Displays during Autotuning
Digital Operator Display
Description
Autotuning
mode selection: T1-01
Using
the same procedures as for the programming
modes
check and set the T1 parameters according to
information
on the previous page.
Be
sure that T1-01 (Autotuning Mode Selection) is set
correctly
and check safety around the motor and
machine.
Motor
base speed: T1-07
(For
rotational autotuning)
The
autotuning start display will appear when all set-
tings
through T1-07 have been completed. The
A.TUNE
and DRIVE indicators will be lit.
Autotuning
started: TUn10
Autotuning
will start when the RUN Key is pressed
from
the autotuning start display.
The
digit second from the right in TUn
oo
is the
Motor
1/2 Selection (T1-00) and the right digit is the
Autotuning
Mode Selection (T1-01).
Autotuning
Stop
command input
If
the STOP Key is pressed or a measurement error
occurs
during autotuning, and error message will be
display
and autotuning will be stopped.
Refer
to Errors during Autotuning on page 7-12.
Autotuning
completed
END
will be displayed after approximately 1 to 2 min-
utes,
indicating that autotuning has been completed.