Communications Functions
6-
111
Inverter
Control
Outputs
(Register
002C
Inverter
Status)
The
Inverter control outputs for register 002C Inverter status are listed in the following table.
Area
Used
by
Operand
of
PMCR
Instruction
The
area used by the operand of the PMCR instruction in the CS-series is shown here.
Word
Slave
1
function
Word
Slave
2
function
Word
Slave
3
function
01100 During
RUN
01200 During
RUN
01300 During
RUN
01101 Zero
speed
01201 Zero
speed
01301 Zero
speed
01102 Frequency
agree
01202 Frequency
agree
01302 Frequency
agree
01103 Custom
speed agree
01203 Custom
speed agree
01303 Custom
speed agree
01104 Frequency
detection 1
01204 Frequency
detection
01304 Frequency
detection
01105 Frequency
detection
01205 Frequency
detection
01305 Frequency
detection
01106 Inverter
ready
01206 Inverter
ready
01306 Inverter
ready
01107 UV
01207 UV
01307 UV
01108 Base
block
01208 Base
block
01308 Base
block
01109 Frequency
reference mode
01209 Frequency
reference mode
01309 Frequency
reference mode
01110 RUN
command mode
01210 RUN
command mode
01310 RUN
command mode
01111 Overtorque
detection
01211 Overtorque
detection
01311 Overtorque
detection
01112 Frequency
reference loss
01212 Frequency
reference loss
01312 Frequency
reference loss
01113 Fault
retry
01213 Fault
retry
01313 Fault
retry
01114 Fault
01214 Fault
01314 Fault
01115 Communications
time-over
01215 Communications
time-over
01315 Communications
time-over
DM
D0100 0 1 1 1 0 0 1 0 1 1 1 0 0 0 0 1
Communications
port 7
Communications
port E1
Word
Control Data: C1
DM
Area
Send Data: S
D1000 000B (Number of Send data items:
11) See note 1.)
D1001 0003 (Number of Slaves)
D1002 0001 (Slave 1 address)
D1003 RUN command to Slave 1
D1004 Frequency reference to Slave 1
0002 (Slave 2 address)
RUN command to Slave 2
Frequency reference to Slave 2
0003 (Slave 3 address)
RUN command to Slave 3
Frequency reference to Slave 3
D1005
D1006
D1007
D1008
D1009
D1010
DM
Area
Recv Data: D
D2000 0003(Number of Recv data items: 3)
See note 2.)
D2001 Slave 1 Inverter status
D2002 Slave 2 Inverter status
D2003 Slave 3 Inverter status
Note 1. Set the number of Send data items in Hex to the number of words of D1000 through D1010 (11).
Note 2. The number of words of D2001 through D2003 is written in Hex for the number of Recv data
items.
Serial port 2
DM
D0101 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Sequence 000 set
Word
Control Data: C2
Summary of Contents for SYSDRIVE 3G3RV
Page 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Page 36: ...1 22...
Page 106: ...3 14...
Page 126: ...4 20...
Page 216: ...5 90...
Page 388: ...7 26...