and sizes of straight solderless terminal are shown in the following table.
Fig 2.21 Straight Solderless Terminal Sizes
n
Wiring
Method
Use
the following procedure to connect wires to the terminal block.
1. Loosen
the terminal screws with a thin-slot screwdriver.
2. Insert
the wires from underneath the terminal block.
3. Tighten
the terminal screws firmly.
Fig 2.22 Connecting Wires to Terminal Block
Table 2.15 Straight Solderless Terminal Sizes
Wire
Size
mm
2
(AWG)
Model
d1
d2
L
Manufacturer
0.25
(24)
AI
0.25 - 8YE
0.8
2
12.5
Phoenix
Contact
0.5
(20)
AI
0.5 - 8WH
1.1
2.5
14
0.75
(18)
AI
0.75 - 8GY
1.3
2.8
14
1.25
(16)
AI
1.5 - 8BK
1.8
3.4
14
2
(14)
AI
2.5 - 8BU
2.3
4.2
14
d2
d1
L
Thin-slot screwdriver
Strip the end for
7 mm if no sold-
erless terminal is
used.
Control circuit
terminal block
Blade of screwdriver
Solderless terminal or wire
without soldering
Wires
3.5 mm max.
Blade thickness: 0.6 mm max.