5
-36
* 1. These
are values for a 200-V class Inverter. Values for a 400-V class Inverter are double.
* 2. The
factory setting will change when the control method is changed. (V/f control factory settings are given.)
* 3. When
C6-01 is set to 0, the upper limit of the setting range is 150.0 Hz.
* 4. For
(-E) models. Factory setting for base frequency is 50 Hz.
E3-08
Motor
2
min.
out-
put
fre-
quency
voltage
(VMIN)
To
set V/f characteristics in a
straight
line, set the same values
for
E3-05 and E3-07.
In
this case, the setting for E3-06
will
be disregarded.
Always
ensure that the four fre-
quencies
are set in the following
manner:
E3-02
(FMAX)
≥
E3-04 (FA) >
E3-05
(FB) > E3-07 (FMIN)
0.0
to
255.0
*1
9.0
V
*1
No
A
A
A
320H
-
Min
Volt-
age
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register
Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
Output voltage (V)
Frequency (Hz)