Parameter Tables
5-
63
n
Torque
Detection:
L6
Parameters
for the torque detection function are shown in the following table.
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
L6-01
Torque
detection
selection
1
0:
Overtorque/undertorque
detection
disabled.
1:
Overtorque detection
only
with speed agree-
ment;
operation continues
after
overtorque
(warning).
2:
Overtorque detected
continuously
during
operation;
operation
continues
after
overtorque
(warning).
3:
Overtorque detection
only
with speed agree-
ment;
output stopped
upon
detection (protected
operation).
4:
Overtorque detected
continuously
during
operation;
output stopped
upon
detection (protected
operation).
5:
Undertorque detection
only
with speed agree-
ment;
operation continues
after
overtorque
(warning).
6:
Undertorque detected
continuously
during
operation;
operation
continues
after
overtorque
(warning).
7:
Undertorque detection
only
with speed agree-
ment;
output stopped
upon
detection (protected
operation).
8:
Undertorque detected
continuously
during
operation;
output stopped
upon
detection (protected
operation).
0
to 8
0
No
A
A
A
4A1H
6-44
Torq
Det 1
Sel
L6-02
Torque
detection
level
1
Open
loop vector control:
Motor
rated torque is set as
100%.
V/f
control: Inverter rated
current
is set as 100%.
0
to
300
150%
No
A
A
A
4A2H
6-44
Torq
Det 1
Lvl
L6-03
Torque
detection
time
1
Sets
the overtorque/under-
torque
detection time in 1-
second
units.
0.0
to
10.0
0.1
s
No
A
A
A
4A3H
6-44
Torq
Det 1
Time
Summary of Contents for SYSDRIVE 3G3RV