Frequency Reference
6-
9
n
Inputting
Frequency
Reference
Using
Current
When
b1-01 is set to 1, you can input the frequency reference from control circuit terminal A2. Input the cur-
rent
(4 to 20 mA) in control circuit terminal A2.
When
H3-09 (Multi-Function Analog Input Terminal A2 Signal Level Selection) is set to 0 (factory setting)
the
input on A2 is added to A1.
Fig 6.8 Frequency Reference Using Current
Setting
Precautions
•
When
inputting a current signal to terminal A2, turn ON pin 2 on DIP switch S1 (factory setting: ON).
•
If
using terminal A2 to input the master speed reference and terminal A1 to input the auxiliary frequency
reference,
set H3-13 (Terminal A1/A2 Switching) to 1.
n
Setting
Frequency
Reference
Using
Pulse
Train
Signals
When
b1-01 is set to 4, the pulse train input to control circuit terminal RP is used as the frequency reference.
Set
H6-01 (PulseTrain Input Function Selection) to 0 (frequency reference), and then set the 100% reference
pulse
frequency to H6-02 (Pulse Train Input Scaling).
Fig 6.9 Frequency Reference Using Pulse Train Input
Inverter
+V (Power supply: 15 V, 20 mA)
A1 (Auxiliary speed frequency
reference)
A2 (Master speed frequency
reference)
AC (Analog common)
1 to 20 mA input
DIP switch S1
Pulse
Input
Specifications
Low
level voltage
0.0
to 0.8 V
High
level voltage
3.5
to 13.2 V
Heavy
duty
30
to 70%
Pulse
frequency
0
to 32 kHz
Inverter
RP(Pulse train input termi-
nal)
AC (Analog common)
32 kHz max.
3.5 to 13.2 V
Pulse input