5
-74
* 1. Set
T1-02 and T1-04 when 2 is set for T1-01. Only set value 2 is possible for V/f control or V/f control with PG.
* 2. These
are values for a 200-V class Inverter. Values for a 400-V class Inverter are double.
* 3. The
factory setting depends on the Inverter capacity. (The value for a 200-V class Inverter for 0.4 kW is given.)
* 4. The
setting range is from 10% to 200% of the Inverter rated output current. (The value for a 200-V class Inverter for 0.4 kW is given.)
* 5. The
upper setting limit will be 150.0 Hz when C6-01 is set to 0.
T1-04
Motor
rated
current
Set
the rated current of the
motor
in amps.
0.32
to
6.40
*4
1.90
A
*3
No
A
A
A
704H
4-13
Rated
Cur-
rent
T1-05
Motor
base
frequency
Set
the base frequency of the
motor
in hertz.
0
to
400.0
*5
60.0
Hz
No
No
No
A
705H
4-13
Rated
Fre-
quency
T1-06
Number
of
motor
poles
Set
the number of motor
poles.
2
to 48
poles
4
poles
No
No
No
A
706H
4-13
Number
of
Poles
T1-07
Motor
base
speed
Set
the base speed of the
motor
in r/min.
0
to
24000
1750
r/min
No
No
No
A
707H
4-13
Rated
Speed
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop