5
-38
K
K
K
K
Option
Parameters:
F
The
following settings are made with the option parameters (F parameters): Settings for Option Cards
n
PG
Option
Setup:
F1
Parameters
for the PG Speed Control Card are shown in the following table.
* Factory
setting for (-E) models is 1024.
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
F1-01
PG
constant Sets the number of PG (pulse
generator
or encoder) pulses.
Sets
the number of pulses
per
motor revolution.
0
to
60000
600
(1024)
*
No
No
Q
No
380H
6-143
PG
Pulses/
Rev
F1-02
Operation
selection
at
PG
open
circuit
(PGO)
Sets
the PG disconnection
stopping
method.
0: Ramp
to stop
(Deceleration
stop using
Deceleration
Time 1, C1-
02.)
1: Coast
to stop
2: Fast
stop (Emergency
stop
using the
deceleration
time in C1-
09.)
3: Continue
operation (To
protect
the motor or
machinery,
do not
normally
make this
setting.)
0
to 3
1
No
No
A
No
381H
6-143
PG
Fdbk
Loss
Sel
F1-03
Operation
selection
at
overspeed
(OS)
Sets
the stopping method
when
an overspeed (OS)
fault
occurs.
0: Ramp
to stop
(Deceleration
stop using
Deceleration
Time 1, C1-
02.)
1: Coast
to stop
2: Fast
stop (Emergency
stop
using the
deceleration
time in C1-
09.)
3: Continue
operation (To
protect
the motor or
machinery,
do not
normally
make this
setting.)
0
to 3
1
No
No
A
No
382H
6-143
PG
Over-
speed
Sel