Parameter Tables
5-
75
K
K
K
K
U:
Monitor
Parameters
The
following settings are made with the monitor parameters (U parameters): Setting parameters for monitor-
ing
in drive mode.
n
Status
Monitor
Parameters:
U1
The
parameters used for monitoring status are listed in the following table.
* The
unit is set in o1-03 (frequency units of reference setting and monitor).
Param-
eter
Number
Name
Description
Output Signal Level Dur-
ing Multi-Function Analog
Output
Min.
Unit
Control Methods
Register
LCD
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
U1-01
Frequency
reference
Monitors/sets
the fre-
quency
reference value.*
10
V: Max. frequency
(0
to ± 10 V possible)
0.01
Hz
A
A
A
40H
Frequency
Ref
U1-02
Output
fre-
quency
Monitors
the output fre-
quency.*
10
V: Max. frequency
(0
to ± 10 V possible)
0.01
Hz
A
A
A
41H
Output
Freq
U1-03
Output
cur-
rent
Monitors
the output current.
10
V: Inverter rated output
current
(0
to +10 V, absolute value
output)
0.1
A
A
A
A
42H
Output
Cur-
rent
U1-04
Control
method
Checks
the current control
method.
(Cannot
be output.)
-
A
A
A
43H
Control
Method
U1-05
Motor
speed
Monitors
the detected motor
speed.*
10
V: Max. frequency
(0
to ± 10 V possible)
0.01
Hz
No
A
A
44H
Motor
Speed
U1-06
Output
volt-
age
Monitors
the output voltage
reference
value in the
Inverter.
10
V: 200 VAC (400 VAC)
(0
to +10 V output)
0.1
V
A
A
A
45H
Output
Volt-
age
U1-07
DC
bus
voltage
Monitors
the main DC volt-
age
in the Inverter.
10
V: 400 VDC (800 VDC)
(0
to +10 V output)
1
V
A
A
A
46H
DC
Bus
Voltage
U1-08
Output
power
Monitors
the output power
(internally
detected value).
10
V: Inverter capacity
(max.
applicable motor
capacity)
(0
to ± 10 V possible)
0.1
kW
A
A
A
47H
Output
kWatts