Parameter Tables
5-
49
n
Analog
Inputs:
H3
Parameters
for analog inputs are shown in the following table.
14
Desired
frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and dur-
ing
frequency agree)
Yes
Yes
Yes
-
15
Frequency
detection 3 (ON: Output frequency
≤
L4-03,
L4-04 used)
Yes
Yes
Yes
-
16
Frequency
detection 4 (ON: Output frequency
≥
L4-03,
L4-04 used)
Yes
Yes
Yes
-
17
Overtorque/undertorque
detection 1 NC (NC Contact: Torque detection at OFF)
Yes
Yes
Yes
6-44
18
Overtorque/undertorque
detection 2 NO (NO Contact: Torque detection at ON)
Yes
Yes
Yes
6-44
19
Overtorque/undertorque
detection 2 NC (NC Contact: Torque detection at OFF)
Yes
Yes
Yes
6-44
1A
During
reverse run (ON: During reverse run)
Yes
Yes
Yes
-
1B
During
baseblock 2 (OFF: During baseblock)
Yes
Yes
Yes
-
1C
Motor
selection (Motor 2 selected)
Yes
Yes
Yes
-
1D
Not
used (Set when the terminals are not used)
Yes
Yes
Yes
-
1E
Restart
enabled (ON: Restart enabled)
Yes
Yes
Yes
6-58
1F
Motor
overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detec-
tion
level)
Yes
Yes
Yes
6-47
20
Inverter
overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting)
Yes
Yes
Yes
-
30
During
torque limit (current limit) (ON: During torque limit)
No
No
Yes
-
37
During
run 2 (ON: Frequency output, OFF: Base block, DC injection braking, ini-
tial
excitation, operation stop)
Yes
Yes
Yes
-
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
H3-01
Signal
select
termi-
nal
A1
(voltage)
0:
Voltage limit enabled
(Below
0 V is 0 V)
1: Voltage
limit disabled
The
setting value 1 can be
set
for (-E) models.
0
or 1
0
No
A
*
A
*
A
*
410H
-
Term
A1
Lvl
Sel
H3-02
Gain
(termi-
nal
A1)
Sets
the frequency when 10
V
is input, as a percentage of
the
maximum output fre-
quency.
0.0
to
1000.0
100.0%
Yes
A
A
A
411H
6-27
Terminal
A1
Gain
H3-03
Bias
(termi-
nal
A1)
Sets
the frequency when 0 V
is
input, as a percentage of
the
maximum frequency.
-100.0
to
+100.0
0.0%
Yes
A
A
A
412H
6-27
Terminal
A1
Bias
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
loop
Vec-
tor
Summary of Contents for SYSDRIVE 3G3RV
Page 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Page 36: ...1 22...
Page 106: ...3 14...
Page 126: ...4 20...
Page 216: ...5 90...
Page 388: ...7 26...