This
section explains how to limit the motor speed.
K
K
K
K
Limiting
Maximum
Output
Frequency
If
you do not want the motor to rotate above a given frequency, use parameter d2-01.
Set
the upper limit value of the Inverter output frequency as a percent, taking E1-04 (Maximum Output Fre-
quency)
to be 100%.
n
Related
Parameters
K
K
K
K
Limiting
Minimum
Frequency
If
you do not want the motor to rotate at below a given frequency, use parameters d2-02 or d2-03.
There
are two methods of limiting the minimum frequency, as follows:
•
Adjust
the minimum level for all frequencies.
•
Adjust
the minimum level for the master speed frequency (i.e., the lower levels of the jog frequency, multi-
step
speed frequency, and auxiliary frequency will not be adjusted).
n
Related
Parameters
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
d2-01
Frequency
reference upper
limit
Set
the output frequency upper limit as a percent,
taking
the max. output frequency to be 100%.
0.0
to
110.0
100.0%
No
A
A
A
Ref
Upper Limit
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
d2-02
Frequency
reference lower
limit
Set
the output frequency lower limit as a percent,
taking
the base reference to be 100%.
0.0
to
110.0
0.0%
No
A
A
A
Ref
Lower Limit
d2-03
Master
speed reference
lower
limit
Set
the master speed reference lower limit as a
percent,
taking the max. output frequency to be
100%.
0.0
to
110.0
0.0%
No
A
A
A
Ref1
Lower Limit