9
-18
n
DC Reactor
A
DC Reactor is used to control harmonics generated by the Inverter. It is more effective than and can be used
in
combination with an AC Reactor. It is also used to increase the power factor.
Models and Application
The
standard models of DC Reactors are listed below.
Inverter
DC Reactor
Voltage
Class
Max. Appli-
cable Motor
Capacity
(kW)
Model No.
Rated
Voltage
(V)
Rated
Current
(A)
Inductance
(mH)
Loss
(W)
200-V
Class
0.4/0.75
3G3HV-PUZDAB5.4A8MH
DC800
5.4
8
8
1.5
to 3.7
3G3HV-PUZDAB18A3MH
18
3
18
5.5/7.5
3G3HV-PUZDAB36A1MH
36
1
22
11/15
3G3HV-
PUZDAB72A0.5MH
72
0.5
29
18.5
3G3HV-
PUZDAB90A0.4MH
90
0.4
45
400-V
Class
0.4/0.75
3G3HV-
PUZDAB3.2A28MH
DC800
3.2
28
9
1.5
to 2.2
3G3HV-
PUZDAB5.7A11MH
5.7
11
11
3.7
3G3HV-
PUZDAB12A6.3MH
12
6.3
16
5.5/7.5
3G3HV-
PUZDAB23A3.6MH
23
3.6
27
11/15
3G3HV-
PUZDAB33A1.9MH
33
1.9
26
18.5
3G3HV-
PUZDAB47A1.3MH
47
1.3
42
Summary of Contents for SYSDRIVE 3G3RV